| Plan Review Notes For Permit 06061761 |
| Permit Number |
06061761 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-10 00:00:00 | 1. CONSTRUCTION, DEMOLTION, AND | | | RENOVATION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3. ONLY TWO EMERGENCY LIGHTS ARE SHOWN | | | ON THE REFLECTED CEILING PLAN. THERE | | | DOES NOT APPEAR TO BE ENOUGH EMERGENCY | | | LIGHT FIXTURES WITHIN THE SPACE. | | | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY FIRE SPRINKLER REMODEL REQUIRED. | | | | | | 5. PLEASE INDICATE ANY EXISTING OR NEW | | | FIRE ALARM HORN STROBES WITHIN THE | | | TENANT SPACE. | | | | | | 6. PLEASE INDICATE LOCATIONS OF PORTABLE | | | FIRE EXTINGUISHERS. | | | | | | 7. PLEASE PROVIDE DETAILS ON FLAME | | | SPREAD FOR THE HANGING CURTAINS THAT | | | SEPARATE THE DRESSING ROOMS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|