| Date |
Text |
| 2006-07-08 00:00:00 | ****** UNSAT ******* |
| | |
| | ** IMPORTANT** |
| | PLEASE SEE NOTE SUNDER PERMIT NUMBER |
| | 06061760 AS THIS IS THE PERMIT FOR |
| | CREATING SHELL SPACE FOR THIS BULD OUT. |
| | PLEASE SEE NOTES BELOW FOR COORDINATION |
| | ISSUES FOR EACH. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW, ONCE ALL REVIEWS |
| | ARE DONE AND BEFORE RSUBMITTING PLANS |
| | ALL OLD/VOIDED SHEETS SHALL BE |
| | COMPLETELTY REMOVED FROM SETS AND ONLY |
| | THE NEW REVISED SHEETS SHALL BE INSERTED |
| | INTO TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONLY ONE SET OF THE OLD/VOIDED |
| | REMOVED SHEETS SHOULD BE SUBMITTED AS |
| | REFERENCE. |
| | 106.1 ADMIN SECT FBC. |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCKS FOR |
| | ARCHITECTURAL FIRM AS REQUIRED UNDER |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| | AND FLORIDA STATUES 481.219 |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER, PRINTED NAME AND |
| | PRINTED LICENSE NUMBER FOR SAID |
| | ARCHITECT ALSO. |
| | PLEASE KNOW, THIS IS REQUIRED ON ALL |
| | PLANS AND FOR ALL SHEETS CONTAINING THIS |
| | TITLE BLOCK WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE ELECTRICAL PLANS FOR |
| | THE BUILD OUT DOES NOT CORRELATE WITH |
| | SCOPE OF WORK AND ELECTRICAL PLANS BEING |
| | DONE FOR SHELL. PLEASE SEE PANELS ARE |
| | SHOWN IN DIFFERENT LOCATIONS, LABELING |
| | ETC. PLEASE SEE THIS SET OF PLANS OWULD |
| | PLACE THE NEW PANELS ETC IN THE FUTURE |
| | BATHRM. |
| | PLEASE SEE 110.26 ETC |
| | PLEASE COORDINATE WITH FUTURE TENANT. |
| | |
| | 4) NOTE: PLEASE SEE THAT ALL THE CURRENT |
| | CODES ARE REFLECTED AS ADOPTED BY THE |
| | STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING SHALL BE INDICATED ON PLANS. |
| | PLEASE ALSO SEE SOME CODES REFLECTED ON |
| | PLANS ARE FROM THE "1996" NEC. |
| | PLEASE REF; 2002 NFPA-70, 2002 NFPA-72, |
| | 2003 NFPA-101, AND 2004 FBC. |
| | |
| | 5) NOTE: PLEASE SEE THE PERMIT FOR |
| | CREATING THIS TENANT SPACE SHOWS THE HV |
| | 277/480V ELECTRICAL PANEL BEING |
| | INSTALLED BY THEM.?? |
| | IN EITHER CASE, AFTER COORDINATION ON |
| | DESIGNERS BEHALF, IF THIS SCOPE OF WORK |
| | IS GOING TO INCLUDE THE INSTALATION OF |
| | PANEL INTO TENANT SPACE. PLEASE IDENTIFY |
| | THE EXISTING LOAD ON THE 1200A MAIN |
| | SHOWN ALONG WITH NEW LOAD OF THIS |
| | TENANT. |
| | PLEASE INCLUDE THE CONDUCTORS FROM |
| | GUTTER TO METER, METER TO MAIN ETC. |
| | IF THE PANEL "H" WHICH IS SHOWN ON THESE |
| | PLANS OR PANEL "A" WHICH IS SHOWN ON THE |
| | OTHER IS GOING TO BE INSTALLED UNDER |
| | THIS PERMIT PLEASE REVISE. |
| | PLEASE INDICATE BY NOTE THAT A |
| | "FLOATING NEUTRAL" SHALL BE INSTALLED. |
| | 250.6,250.24B,310.16,240.4, 215.5, ETC |
| | |
| | 6) NOTE: PLEASE INDICATE THE AIC RATING |
| | FOR NEW MAIN. |
| | 110.9. |
| | |
| | 7) NOTE: PLEASE SEE COLOR CODING FOR THE |
| | 277/480/V SHALL BE BROWN, PURPLE, |
| | YELLOW. |
| | FOR ABC PHASES. |
| | |
| | 8) NOTE: PLEASE SEE PANEL SCHEDULES AND |
| | RISER AS MANY ITEMS ARE VERY LIGHT IN |
| | THE PRINT AND EASILY READABLE. |
| | PLEASE BE SURE PLANS ARE RE-PRINTED TO |
| | BE CLEAR AND VISABLE. |
| | 106.1.3 ADMIN SECT |
| | |
| | 9) NOTE: PLEASE VERIFY THE CONTINUOUS |
| | LOADS AT 125%. A DEMAND IS SHOWN, AND |
| | APPEARS TO BE THE 125%, HOWEVER IF SO, |
| | PLEASE INDICATE. |
| | 215.3,230.42 ETC |
| | |
| | 10) NOTE: PLEASE CLARIFY LOADS ON TRACK |
| | LTS, IF THE LOADS ARE INDEED SHOWN PER |
| | 220.12. |
| | PLEASE ADJUST CALCULATIONS IF NEEDED. |
| | |
| | 11) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM PANEL "H" TO |
| | TRANSFORMER. |
| | 250.110,250.122 |
| | |
| | 12) NOTE: PLEASE CLARIFY WHERE THE NEW |
| | SIGN CIRCUIT IS LOCATED.? |
| | 600.5 |
| | |
| | 13) NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SHOW THE TIME SCHEDULING, THE |
| | LOCATION OF THE REQUIRED PVER RIDES |
| | DEVICES, AND THE TYPE OF PROPOSED OVER |
| | RIDE DEVICES. |
| | PLEASE KNOW, IF A TIMER TYPE, A MAX OF |
| | 4HRS SHALL BE INDICATED. IF AN OCC |
| | SENSORS, MOTION TYPE DEVICE ETC IS BEING |
| | SHOWN , A MAX TIME OF 30 MINS SHALL BE |
| | INDICATED. |
| | |
| | 14) NOTE: PLEASE VERIFY TRANSFORMER |
| | LOCATION, AS IT APPEARS TO BE SHOWN IN |
| | BATHRM? |
| | PLEASE ALSO INDICATE THE STRUCTURAL |
| | DETAIL ON MOUNTING THIS |
| | UNIT.;(WALL,CEILING ECT). |
| | |
| | 15) NOTE: PLEASE CORRELATE ADDRESS AND |
| | SUITE # WHICH IS GOING TO BE FOR THIS |
| | UNIT, AS TITLE BLOCK INDICATES SUITE # |
| | 128 AND PERMIT APPLICATION INDICATES |
| | #126? |
| | PLEASE KNOW, IF 126, THEN ADJUST PLANS. |
| | 106.1.2 |
| | |
| | PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2006-07-07 00:00:00 | ** ELECTRICAL REVIEW IN PROGRESS |