Plan Review Notes
Plan Review Notes For Permit 06061761
Permit Number 06061761
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-08 00:00:00****** UNSAT *******
  
 ** IMPORTANT**
 PLEASE SEE NOTE SUNDER PERMIT NUMBER
 06061760 AS THIS IS THE PERMIT FOR
 CREATING SHELL SPACE FOR THIS BULD OUT.
 PLEASE SEE NOTES BELOW FOR COORDINATION
 ISSUES FOR EACH.
  
  
 1) NOTE: PLEASE KNOW, ONCE ALL REVIEWS
 ARE DONE AND BEFORE RSUBMITTING PLANS
 ALL OLD/VOIDED SHEETS SHALL BE
 COMPLETELTY REMOVED FROM SETS AND ONLY
 THE NEW REVISED SHEETS SHALL BE INSERTED
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONLY ONE SET OF THE OLD/VOIDED
 REMOVED SHEETS SHOULD BE SUBMITTED AS
 REFERENCE.
 106.1 ADMIN SECT FBC.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS FOR
 ARCHITECTURAL FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUES 481.219
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, PRINTED NAME AND
 PRINTED LICENSE NUMBER FOR SAID
 ARCHITECT ALSO.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 PLANS AND FOR ALL SHEETS CONTAINING THIS
 TITLE BLOCK WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE ELECTRICAL PLANS FOR
 THE BUILD OUT DOES NOT CORRELATE WITH
 SCOPE OF WORK AND ELECTRICAL PLANS BEING
 DONE FOR SHELL. PLEASE SEE PANELS ARE
 SHOWN IN DIFFERENT LOCATIONS, LABELING
 ETC. PLEASE SEE THIS SET OF PLANS OWULD
 PLACE THE NEW PANELS ETC IN THE FUTURE
 BATHRM.
 PLEASE SEE 110.26 ETC
 PLEASE COORDINATE WITH FUTURE TENANT.
  
 4) NOTE: PLEASE SEE THAT ALL THE CURRENT
 CODES ARE REFLECTED AS ADOPTED BY THE
 STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING SHALL BE INDICATED ON PLANS.
 PLEASE ALSO SEE SOME CODES REFLECTED ON
 PLANS ARE FROM THE "1996" NEC.
 PLEASE REF; 2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101, AND 2004 FBC.
  
 5) NOTE: PLEASE SEE THE PERMIT FOR
 CREATING THIS TENANT SPACE SHOWS THE HV
 277/480V ELECTRICAL PANEL BEING
 INSTALLED BY THEM.??
 IN EITHER CASE, AFTER COORDINATION ON
 DESIGNERS BEHALF, IF THIS SCOPE OF WORK
 IS GOING TO INCLUDE THE INSTALATION OF
 PANEL INTO TENANT SPACE. PLEASE IDENTIFY
 THE EXISTING LOAD ON THE 1200A MAIN
 SHOWN ALONG WITH NEW LOAD OF THIS
 TENANT.
 PLEASE INCLUDE THE CONDUCTORS FROM
 GUTTER TO METER, METER TO MAIN ETC.
 IF THE PANEL "H" WHICH IS SHOWN ON THESE
 PLANS OR PANEL "A" WHICH IS SHOWN ON THE
 OTHER IS GOING TO BE INSTALLED UNDER
 THIS PERMIT PLEASE REVISE.
 PLEASE INDICATE BY NOTE THAT A
 "FLOATING NEUTRAL" SHALL BE INSTALLED.
 250.6,250.24B,310.16,240.4, 215.5, ETC
  
 6) NOTE: PLEASE INDICATE THE AIC RATING
 FOR NEW MAIN.
 110.9.
  
 7) NOTE: PLEASE SEE COLOR CODING FOR THE
 277/480/V SHALL BE BROWN, PURPLE,
 YELLOW.
 FOR ABC PHASES.
  
 8) NOTE: PLEASE SEE PANEL SCHEDULES AND
 RISER AS MANY ITEMS ARE VERY LIGHT IN
 THE PRINT AND EASILY READABLE.
 PLEASE BE SURE PLANS ARE RE-PRINTED TO
 BE CLEAR AND VISABLE.
 106.1.3 ADMIN SECT
  
 9) NOTE: PLEASE VERIFY THE CONTINUOUS
 LOADS AT 125%. A DEMAND IS SHOWN, AND
 APPEARS TO BE THE 125%, HOWEVER IF SO,
 PLEASE INDICATE.
 215.3,230.42 ETC
  
 10) NOTE: PLEASE CLARIFY LOADS ON TRACK
 LTS, IF THE LOADS ARE INDEED SHOWN PER
 220.12.
 PLEASE ADJUST CALCULATIONS IF NEEDED.
  
 11) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM PANEL "H" TO
 TRANSFORMER.
 250.110,250.122
  
 12) NOTE: PLEASE CLARIFY WHERE THE NEW
 SIGN CIRCUIT IS LOCATED.?
 600.5
  
 13) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SHOW THE TIME SCHEDULING, THE
 LOCATION OF THE REQUIRED PVER RIDES
 DEVICES, AND THE TYPE OF PROPOSED OVER
 RIDE DEVICES.
 PLEASE KNOW, IF A TIMER TYPE, A MAX OF
 4HRS SHALL BE INDICATED. IF AN OCC
 SENSORS, MOTION TYPE DEVICE ETC IS BEING
 SHOWN , A MAX TIME OF 30 MINS SHALL BE
 INDICATED.
  
 14) NOTE: PLEASE VERIFY TRANSFORMER
 LOCATION, AS IT APPEARS TO BE SHOWN IN
 BATHRM?
 PLEASE ALSO INDICATE THE STRUCTURAL
 DETAIL ON MOUNTING THIS
 UNIT.;(WALL,CEILING ECT).
  
 15) NOTE: PLEASE CORRELATE ADDRESS AND
 SUITE # WHICH IS GOING TO BE FOR THIS
 UNIT, AS TITLE BLOCK INDICATES SUITE #
 128 AND PERMIT APPLICATION INDICATES
 #126?
 PLEASE KNOW, IF 126, THEN ADJUST PLANS.
 106.1.2
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
2006-07-07 00:00:00** ELECTRICAL REVIEW IN PROGRESS