Plan Review Notes
Plan Review Notes For Permit 06061760
Permit Number 06061760
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-05 00:00:00******* UNSAT *******
  
 1) NOTE: PLEASE SEE SHEET A1.0 DOES NOT
 CONTAIN THE "CITY PLACE REVIEW STAMP"
 THIS WAS A REQUIREMENT PER CITY PLACE
 PARTNERS THROUGH THE CITY AND IS NOT A
 CODE COMMENT. PLEASE KNOW, NO PLANS CAN
 BE STAMPED AND PERMITTED UNLESS ALL
 SHEETS CONTAIN SUCH STAMP.
  
 2) NOTE: PLEASE SEE ADDRESSING ON PLANS
 STILL DOES NOT CORRELATE WITH ACTUAL
 "SUITE 3'S. PLEASE KNOW, ALL ARE A THREE
 DIGIT SUITE # AS PREVIOUSLY NOTED.
  
 3) NOTE: PLEASE SEE RISER DIAGRAM SHOWS
 AND INDICATES A NEW PANEL YET, PLEASE
 SEE PLANS DO NOT INDICATE THIS NEW
 EQUIPMENT.
 110.26,240.24, ETC
  
 4) NOTE: PLEASE SEE NEW WALLS BEING
 ADDED, NEED TO VERIFY THE EXISITNG
 ELECTRICAL EQUIPMENT LOCATION. IT WAS
 REMEMBERED THIS WAS SHOWN ON PREVIOUS
 PLANS.
 110.26, 408.7, 240.24 ETC
  
 **PLEASE BE SURE TO COMPLETELY REMOVE
 ANY OLD/VOIDED SHEETS AND ONLY INSERT
 NEW REVISED SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  