| 2006-07-08 00:00:00 | ****** UNSAT ******* |
| | |
| | ** IMPORTANT** |
| | PLEASE SEE NOTE SUNDER PERMIT NUMBER |
| | 06061761 AS THIS IS THE FUTURE BUILD OUT |
| | FOR THIS SPACE. PLEASE SEE NOTES BELOW |
| | FOR CORDINATION ISSUES FOR EACH. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW, ONCE ALL REVIEWS |
| | ARE DONE AND BEFORE RSUBMITTING PLANS |
| | ALL OLD/VOIDED SHEETS SHALL BE |
| | COMPLETELTY REMOVED FROM SETS AND ONLY |
| | THE NEW REVISED SHEETS SHALL BE INSERTED |
| | INTO TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONLY ONE SET OF THE OLD/VOIDED |
| | REMOVED SHEETS SHOULD BE SUBMITTED AS |
| | REFERENCE. |
| | 106.1 ADMIN SECT FBC. |
| | |
| | 2) NOTE: PLEASE SEE PERMIT APPLICATION |
| | MENTIONS "TENANT BLD-OUT" ALTHOUGH SCOPE |
| | OF WORK SEEMS TO BE ONLY TO CREATE NEW |
| | TEANANT DEMISING WALL/TENANT SEPARATION |
| | FOR "FUTURE TENANT BUILD OUT". |
| | PLEASE ADJUST SCOPE OF WORK ON PLANS, OR |
| | PERMIT APPLICATION. |
| | 106..1 |
| | |
| | 3) NOTE: PLEASE SEE ELECTRICAL PLANS FOR |
| | THE FUTURE BUILD OUT DOES NOT CORRELATE |
| | WITH SCOPE OF WORK. PLEASE SEE PANELS |
| | ARE SHOWN IN DIFFERENT LOCATIONS, |
| | LABELING ETC. PLEASE SEE THIS SET OF |
| | PLANS WOULD PLACE THE NEW PANELS ETC IN |
| | THE FUTURE BATHRM. |
| | PLEASE SEE 110.26 ETC |
| | PLEASE COORDINATE WITH FUTURE TENANT. |
| | |
| | 4) NOTE: PLEASE SEE PLANS SUBMITTED SHOW |
| | TWO COMPLETELY DIFFERENT ADDRESSES?? |
| | SOME SHEETS INDICATE 700 S ROSEMARY AND |
| | OTHERS 600 S ROSEMARY. |
| | THE FUTURE TENANTS ADDRESS SEEMS TO BE |
| | 700". PLEASE ALSO SEE THE SUITE # SHOWN |
| | ON PLANS IS NOT CORRECT. PLEASE SEE THE |
| | THREE DIGIT SUITE EXTENSIONS GIVEN AND |
| | ADJUST TITLE BLOCKS ON ALL SHEETS. |
| | |
| | 5) NOTE: PLEASE SEE FUTURE TENANT SHOWS |
| | THE ELECTRICAL PANEL BEING INSTALLED BY |
| | THEM>?? |
| | IN EITHER CASE, AFTER CORDINATION ON |
| | DESIGNERS BEHALF, IF THIS SCOPE OF WORK |
| | IS GOING TO INCLUDE THE INSTALLATION OF |
| | PANEL INTO TENANT SPACE. PLEASE IDENTIFY |
| | THE EXISTING LOAD ON THE 1200A MAIN |
| | SHOWN ALONG WITH NEW LOAD OF THIS |
| | TENANT. |
| | PLEASE INCLUDE THE CONDUCTORS FROM |
| | GUTTER TO METER, METER TO MAIN. PLEASE |
| | INDICATE BY NOTE THAT A "FLOATING |
| | NEUTRAL" SHALL BE INSTALLED. |
| | 250.6,250.24B,310.16,240.4, 215.5, ETC |
| | |
| | 6) NOTE: PLEASE INDICATE THE AIC RATING |
| | FOR NEW MAIN. |
| | 110.9. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-07-07 00:00:00 | ** ELECTRICAL REVIEW IN PROGRESS |