| Plan Review Notes For Permit 06061717 |
| Permit Number |
06061717 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-03 00:00:00 | *****DENIED***** | | | | | | | | | 1.) CONTRARY TO YOUR COMMENT RESPONSE | | | SHEET DATED AUGUST 30TH,2006, THE | | | RESUBMITTED PLANS STILL REFLECT THAT THE | | | SCOPE OF THE WORK WILL ENTAIL THAT THE | | | CONDUIT (ALTHOUGH ENCLOSED IN A 2 HOUR | | | RATED CHASE) PENETRATES A FIRE RATED | | | STAIRWELL.AS STATED IN THE PREVIOUS | | | FIRE PLAN REVIEW, PENETRATIONS INTO, AND | | | OPENINGS THROUGH, AN EXIT ENCLOSURE | | | ASSEMBLY SHALL BE LIMITED TO THOSE AS | | | RECORDED IN NFPA 101, 2003 EDITION, | | | SECTION 7.1.3.2.1.(6). | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|