| Date |
Text |
| 2006-10-04 00:00:00 | **** PLEASE SEE 300.19A FOR SIZE AND |
| | LENGTH OF CONDUCTORS. |
| | SUPPORTS WHICH WOULD REQUIRE SOME TYPE |
| | OF PULL BOXES, WOULD NOT BE PERMITTED IN |
| | STAIRTOWERS. |
| 2006-09-18 00:00:00 | **** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME NOTE FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO |
| | INFORMATION ON PLANS. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECLTY FROM PREVIOUS REVIEW WITH NEW |
| | NOTES ADDED AT THE BOTTOM. |
| | |
| | |
| | |
| | |
| | 1) NOTE: NO, EXISTING RISER, OCP, SIZE |
| | ETC STILL NEEDS TO BE SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY AND SPECIFY THE |
| | TYPE OF EM DISTRIBUTION SYSTEMTHIS NEW |
| | PROPOSED CONNECTION IS COMING FROM. |
| | PLEASE KNOW, AS SHOWN THIS MAY NOT BE |
| | TAPPED FROM THE EXISTING EM DIST SYSTEM. |
| | PLEASE KNOW THERE IS MUCH INFORMATION |
| | NOT SUBMITTED FOR CONSIDERATION TO DO |
| | SO. |
| | 700,701,NFPA-110CHAPTERS 5,6,7. |
| | |
| | 2) NOTE:NO, PLEASE SEE DETAIL AS SHOWN |
| | FOR STAIRS IS STILL IN QUESTION, AND |
| | CONFORMATION WITH THE BUILDING REVIEW |
| | APPEARS THE SIZE OF REQUESTED ENCLOSURE |
| | IS TOO LARGE IN STAIRS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE BUILDING AND FIRE |
| | REVIEW COMMENTS, AS CONDUITS SHOWN ARE |
| | BEING PROPOSED IN THE STAIR WAYS WHICH |
| | ARE NOT PERMITTED. NO EXCEPTIONS. |
| | |
| | 3) NOTE:NO, PLEASE KNOW THAT NO |
| | VERIFICATION OF EXISTING CAN BE DONE AS |
| | THE PERMITTING , INSTALLATION AND |
| | UPGRADE FOR EXISTING OLD GENERATOR IS |
| | NOT YET DONE. |
| | ** PLEASE SEE NOTE WHICH MENTIONS "KEMM" |
| | CONSULTING.? PLEASE VERIFY ,AS THIS MAY |
| | BE A MISPRINT FOR NAME. |
| | PLEASE KNOW, AS THESE ARE NOW PART OF A |
| | LEGALLY REQUIRED SYSTEM, SIZING , |
| | LOCATION ETC MUST BE VERIFIED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | |
| | PLEASE PROVIDE LOAD |
| | CALCULATIONS FOR ALL PROPOSED LOADS |
| | BEING ADDED TO EXISTING LOADS. |
| | DEPENDING ON THE CONNECTIONS OF THE EM |
| | DIST SYSTEM AND TRANSFER DEVICES ETC, IT |
| | IS KNOWN TO THIS OFFICE THAT THIS |
| | BUILDING (MARRIOTT HOTEL) IS CURRENTLY |
| | PROPOSING THE INSTALLATION OF A NEW EM |
| | GEN AND DIST SYSTEM WHICH IS NOT YET |
| | PERMITTED. |
| | PLEASE KNOW, COMPLETE LOAD CALCS AND/OR |
| | DEMANDS AND NEW LOADS ARE REQUIRED AT |
| | THIS TIME. THERE WILL BE NO EXCEPTIONS |
| | OR "PROVISOS" (CONDITION TO ISSUE) |
| | GRANTED. |
| | 220, 215.5, ETC |
| | 106.1.2 FBC ADMIN SECT |
| | |
| | 4) NOTE: NO, PLEASE SEE PLANS STILL |
| | INDICATE THE 2005. THIS WAS REDLINED AND |
| | HIGHLIGHTED ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NTOE ** |
| | PLEASE SEE PLANS CURRENTLY CALL |
| | FOR THE 2005 NEC. PLEASE KNOW, THE STATE |
| | OF FLORIDA IS STILL CURRENTLY UNDER |
| | UNDER THE 2002 NFPA-70 |
| | |
| | 5) NOTE: NO?? THIS IS IN QUESTION , AS |
| | ALL EQUIPMENT BEING SHOWN ON PLANS AND |
| | LABOUR FOR INSTALLATION SEEMS TO BE |
| | HIGHER THAN SHOWN ON APPLICATION. |
| | SIGNED, DATED AND NOTARIZED CONTRACT(S) |
| | ARE REQUIRED. FBC 108.3. |
| | THIS SCOPE IS FOR ALL ELECTRICAL , |
| | BUILDING, MECHANICALETC. |
| | |
| | ** PLEASE SEE VALUE SHALL BE BASED |
| | ON ALL LABOR AND MATERIALS, EVEN IF ANY |
| | OF THE EQUIPMENT OR MATERIALS ARE OWNER |
| | SUPPLIED. PLEASE KNOW, IF VALUE IS NOT |
| | ADJUSTED, ONE WILL BE ASSESSED BY THIS |
| | OFFICE USING GUIDES AS ADOPTED INTO THE |
| | FBC. 108.3 ADMIN SETC. |
| | |
| | 6) NOTE: NO, PLEASE SEE SOME NOTES SHOWN |
| | ON SHEETS DO NOT CORRELATE WITH "CODED |
| | NOTES", PLEASE SEE UNABLE TO VERIFY SOME |
| | ITEMS. |
| | 240.21, PANEL ON SECONDARY SIDE OF THE |
| | TRANSFORMER ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE COMPLETE PLANS , NOTES |
| | AND RISER. PLEASE SEE THERE ARE |
| | NUMERICAL NOTES ON PLANS WHICH ARE SHOWN |
| | SHOWN ON NOTES.. PLEASE PLACE NOTES AND |
| | INFORMATION ON RISER. THIS WILL HELP THE |
| | REVIEW PROCESS OF JUMPING BACK AND FORTH |
| | FROM PAGES. PLEASE SEE NOTES ONLY GO |
| | THROUGH 24. |
| | 106.1.2.,90.7 |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: OK. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWER(S). |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT CODE COMPLIANT |
| | COMMENTS. THIS IS ONLY NOTED AT THIS |
| | TIME. |
| | |
| | ** IMPORTANT** |
| | |
| | ONCE ALL REVIEWS ARE DONE, PLANS ARE |
| | PICKED UP AND BEFORE RESUBMITTING. |
| | PLEASE COMPLETELY REMOVED ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONLY ONE COPY OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED BACK FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |