| 2006-07-21 00:00:00 | ************ UNSAT **************** |
| | |
| | ** PLEASE SEE THE FOLLOWING COMMENTS AS |
| | THE DESIGN AS SHOWN WILL NOT BE |
| | PERMITTED AND CHANGES WILL BE REQUIRED. |
| | |
| | 1) NOTE: PLEASE CLARIFY AND SPECIFY THE |
| | TYPE OF EM DISTRIBUTION SYSTEMTHIS NEW |
| | PROPOSED CONNECTION IS COMING FROM. |
| | PLEASE KNOW, AS SHOWN THIS MAY NOT BE |
| | TAPPED FROM THE EXISTING EM DIST SYSTEM. |
| | PLEASE KNOW THERE IS MUCH INFORMATION |
| | NOT SUBMITTED FOR CONSIDERATION TO DO |
| | SO. |
| | 700,701,NFPA-110CHAPTERS 5,6,7. |
| | |
| | 2) NOTE: PLEASE SEE BUILDING AND FIRE |
| | REVIEW COMMENTS, AS CONDUITS SHOWN ARE |
| | BEING PROPOSED IN THE STAIR WAYS WHICH |
| | ARE NOT PERMITTED. NO EXCEPTIONS. |
| | |
| | 3) NOTE: PLEASE PROVIDE LOAD |
| | CALCULATIONS FOR ALL PROPOSED LOADS |
| | BEING ADDED TO EXISTING LOADS. |
| | DEPENDING ON THE CONNECTIONS OF THE EM |
| | DIST SYSTEM AND TRANSFER DEVICES ETC, IT |
| | IS KNOWN TO THIS OFFICE THAT THIS |
| | BUILDING (MARRIOTT HOTEL) IS CURRENTLY |
| | PROPOSING THE INSTALLATION OF A NEW EM |
| | GEN AND DIST SYSTEM WHICH IS NOT YET |
| | PERMITTED. |
| | PLEASE KNOW, COMPLETE LOAD CALCS AND/OR |
| | DEMANDS AND NEW LOADS ARE REQUIRED AT |
| | THIS TIME. THERE WILL BE NO EXCEPTIONS |
| | OR "PROVISOS" (CONDITION TO ISSUE) |
| | GRANTED. |
| | 220, 215.5, ETC |
| | 106.1.2 FCB ADMIN SECT |
| | |
| | 4) NOTE: PLEASE SEE PLANS CURRENTLY CALL |
| | FOR THE 2005 NEC. PLEASE KNOW, THE STATE |
| | OF FLORIDA IS STILL CURRENTLY UNDER |
| | UNDER THE 2002 NFPA-70 |
| | |
| | 5) NOTE: PLEASE SEE VALUE SHALL BE BASED |
| | ON ALL LABOR AND MATERIALS, EVEN IF ANY |
| | OF THE EQUIPMENT OR MATERIALS ARE OWNER |
| | SUPPLIED. PLEASE KNOW, IF VALUE IS NOT |
| | ADJUSTED, ONE WILL BE ASSESSED BY THIS |
| | OFFICE USING GUIDES AS ADOPTED INTO THE |
| | FBC. 108.3 ADMIN SETC. |
| | |
| | 6) NOTE: PLEASE COMPLETE PLANS , NOTES |
| | AND RISER. PLEASE SEE THERE ARE |
| | NUMERICAL NOTES ON PLANS WHICH ARE SHOWN |
| | SHOWN ON NOTES.. PLEASE PLACE NOTES AND |
| | INFORMATION ON RISER. THIS WILL HELP THE |
| | REVIEW PROCESS OF JUMPING BACK AND FORTH |
| | FROM PAGES. PLEASE SEE NOTES ONLY GO |
| | THROUGH 24. |
| | 106.1.2.,90.7 |
| | |
| | 7) NOTE: PLEASE CLARIFY TITLE BLOCKS AS |
| | ADDRESSING INFORMATION FOR SAID ENGINEER |
| | AND FIRM DO NOT SEEM TO CORRELATE WITH |
| | THE STATE'S WEBSITE. PLEASE SEE ATTACHED |
| | COPIES PRINTED FROM THE DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION. |
| | FAC 61G15-23.002, FS 471 |
| | |
| | 8) NOTE: PLEASE SEE LOCATION OF PROJECT |
| | IS NOTED AS "PB MARKETPLACE"?? THIS |
| | BUIDLING IS THE MARRIOTT HOTEL. PLEASE |
| | ADJUST TITLE BLOCKS. |
| | FAC 61G15-23.002 |
| | |
| | PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWER(S). |
| | |
| | ** IMPORTANT** |
| | |
| | ONCE ALL REVIEWS ARE DONE, PLANS ARE |
| | PICKED UP AND BEFORE RESUBMITTING. |
| | PLEASE COMPLETELY REMOVED ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONLY ONE COPY OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED BACK FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |