| 2006-09-24 00:00:00 | ******** UNSAT 2ND REVIEW ************ |
| | |
| | ** PLEASE SEE MOST NOTES FROM PREVIOUS |
| | REVIEW STILL APPLY ALONG WITH SOME NEW |
| | COMMENTS DUE TO CHANGES IN PLANS. |
| | **PLEASE SEE THE EXACT SAME PLANS WERE |
| | SUBMITTED BACK WITH OUT CODE CORRECTIONS |
| | BEING MADE.?? |
| | |
| | 1) NOTE:NO, A VALUE WAS CHANGED ON |
| | APPLICATIONWAS INCREASED TO $55K, |
| | HOWEVER THIS VALUE IS WAY LOW. PLEASE |
| | KNOW, IF THIS IS NOT ADJUSTED |
| | APPROPRIATLY, ONE WILL BE ASSESSED BASED |
| | ON THE MARSHALLS & SWIFT GUIDE AND |
| | TODAYS CURRENT RATES ADOPTED INTO TEH |
| | FBC. 108.3. |
| | THE VALUE ON THE GENERATO ALONE IS |
| | HIGHER THAN THAT GIVEN, WHICH DOES NOT |
| | INCLUDE THE $10K+ ATS, , SLAB, AND |
| | LABOUR. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE VALUE FOR |
| | COMPLETE SCOPE OF WORK SHALL BE |
| | INLCUDED. PLEASE KNOW, EVEN IF ANY |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | FBC 108.3 , ADMIN SECT. |
| | PLEASE ADJUSTOR ONE WILL BE ASSESSED |
| | PER MARSHALL'S SWIFT GUIDE AS ADOPTED |
| | UNDER THE FBC. |
| | |
| | 2) NOTE: SUBMITTED, HOWEVER THIS WILL BE |
| | REVIEWED BY BUILDING. PLEASE SEE THAT |
| | THE ELEVATIONS FOR THIS MUST BE A MINOF |
| | 6" ABOVE BFE. THIS IS NOT YET INDICATED |
| | ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE SLAB INFORMATION |
| | AT THIS TIME. PLEASE KNOW, THE SIZE, TIE |
| | DOWN ETC FOR GEN AND SLAB INFORMATION IS |
| | REQUIRED AT THIS TIME BEFORE PERMIT FOR |
| | GENERATOR CAN BE ISSUED. |
| | PLEASE SEE BUIDLING REVIEW COMMENTS. |
| | 106.1.2 |
| | |
| | 3) NOTE:NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE AND CLARIFY |
| | ATS BEING INSTALLED. NO |
| | SPES/MANUFCATURES CUT SHEETS WERE |
| | SUBMITTED FOR REVIEW. PLEASE SEE A PRINT |
| | OUT FROM AN WEBSITE INDICATE AN "ONAN" |
| | YET PLANS CALL FOR GENERAC ATS WHICH |
| | WOULD CORRELATE WITH THE LISTED GENERAC |
| | GENERATOR. |
| | PLEASE CORRELATE AND SUBMIT ALL |
| | INFORMATION. |
| | PLEASE SEE MISSING WP HOUSING SPECS. |
| | PLEASE BE SURE MIN CLEARENCES ARE |
| | INDICATE FOR GEN AND PLEASE BE SURE AIC |
| | RATINGS FOR ALL EQUIPMENT IS SHOWN. |
| | 110.9,702.6,215.5,110.26,110.3,90.7 ETC |
| | |
| | 4) NOTE: NO, SEEMS TO BE SUBMITTED, |
| | HOWEVER LISTINGS TO BE VERIFIED. |
| | PLEASE SEE NO CALCULATIONS WERE |
| | SUBMITTED FOR FUEL USESAGE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE SPECS/CUT |
| | SHEET FOR FUEL TANK AND SIZE. PLEASE |
| | INDICATE GPH USESAGE AND SHOW ON PLANS. |
| | PLEASE KNOW, EVEN THOUGH THE FUEL PERMIT |
| | WILL BE SEPARATE THIS INFORMATION IS |
| | REQUIRED AT THIS TIME. PLEASE ALSO SEE |
| | MECH REVIEW AND FIRE REVIEW COMMENTS. |
| | 110.3,90.7, |
| | 106.1.2 FBC |
| | |
| | 5) NOTE: NO, SAME NOTE> |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE SPECIFY THE NFPA-110 |
| | PLEASE SEE CHAPTER 27 OF THE 2004 FBC, |
| | AND 2002 110. |
| | |
| | 6) NOTE: NO, THIS WAS DONE, HOWEVER THIS |
| | INFORMATION WAS HANDWRITTEN ON PLANS |
| | WHICH IS NOT PERMITTED. PLEASE BES URE |
| | THE ENGINEER OF RECORD MAKES THE |
| | REQUIRED CHANGES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW AND INDICATE ALL |
| | SETBACKS FOR GENERATOR AND EQUIPMENT. |
| | 106.1.2 |
| | |
| | 7) NOTE:NO, SAME NOTE. NOT ENNOUGH |
| | INFORMATION SUBMITTED FOR COMPLETE |
| | REVIEW AND CODE COMPLIANCE IS NOT YET |
| | MET. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY IF THE EXISTING |
| | MAIN PANEL WHERE IT APPEARS TO BE |
| | LOCATED ADJACENT TO THE NEW SE RATED ATS |
| | CONTAINS A MAIN? |
| | PLEASE ALSO PROVIDE INFORMATION BY THE |
| | WAY OF THE SPECS TO BE SUBMITTED AND |
| | PLANS THAT THE ATS CONTAINS A MANUAL |
| | MEANS OF DISCONNECT RATED FOR THE LOAD |
| | SERVED ON THE OUTSIDE AS REQUIRED PER |
| | 230.70,230.76,230.79. |
| | PLEASE KNOW, IF THE EXISTING MAIN PANEL |
| | DOES NOT CONTAIN MCB, AND THE ATS DOES |
| | NOT DISCONNECT POWER FROM BOTH NORMAL |
| | AND EM SIDES TO A CENTER OFF POSITION, A |
| | MEANS OF DISCONNECT WILL BE REQUIRED |
| | LOCATED AT BUIDLING GROUPED WITH OUTHER |
| | MAINS. |
| | 225.31-225.39, 230.72, 230.70 |
| | |
| | |
| | ** NEW NOTRES** |
| | |
| | 8) NOTE: PLEASE SEE ONLY ONE SET OF |
| | PLANS ARE SIGNED, DATED AND SEALED. |
| | PLEASE SEE FAC 61G15-23.002, FS 471.025. |
| | |
| | 9) NOTE: PLEASE SEE AS THE SAME PLANS |
| | ORIGINAL SUBMITTED WERE BROUGHT BACK |
| | WITH HAND DRAWN CHANGES ON SOME SHEETS, |
| | AND NOT CORRECTIONS MADE, ONE SET OF |
| | PLANS ARE BEING RETAINED FOR FILE FOR |
| | POSSIBLE REVIEW BY THE FBPE'S. |
| | PLEASE SEE FS 553.80(2)(B) WITH RESPECT |
| | TO REPEAT CODE COMPLIANT COMMENTS FOR |
| | DESIGN PREOFESSIONALS. |
| | |
| | 10) NOTE: PLEASE SEE THE NOTICE OF |
| | COMMENCMENT SUBMITTED IS NO LONGER VALID |
| | AND IS NULL AND VOID. PLEASE SEE FS |
| | 713.13(2). WHEN WORK HAS NOT COMMENCED |
| | WITHIN 90 DAYS OF RECORDING SUCH NOC, |
| | THEN THE DOCUMENT OF VOID> |
| | ** THE RECORDED NOC IS ONLY REQUIRED |
| | WHEN PICKING UP PERMIT. |
| | |
| | |
| | PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL AND OTHER |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |