| 2006-08-21 00:00:00 | DENIED:DIESEL GENRATOR |
| | ELECTICAL PERMIT 06061709 |
| | |
| | 1.PLEASE PROVIDE INFORMATION ON THE |
| | GENERATOR'S FUEL TANK, I.E. SUB-BASE, |
| | ABOVE GROUND, UNDERGROUND, CAPACITY, |
| | ETC. |
| | |
| | 2.PROVIDE INFORMATION FOR THE FUEL |
| | PIPING, SIZE, MATERIAL, LAYOUT, SUPPORT, |
| | ETC. |
| | |
| | 3.INDICATE DISTANCES/CLEARANCES FROM |
| | THE GENERATOR TO PROPERTY LINES, |
| | BUILDINGS, FRESH AIR INTAKES, WINDOWS, |
| | DOORS, LOUVERS, ETC.SHOW COMPLIANCE |
| | WITH 2004 FMC 401.5, 401.5.1 & 501.2. |
| | |
| | 4.ADDITIONAL PERMIT FOR THE FUEL OIL |
| | STORAGE, IF THIS IS NOT A SUB-BASE FUEL |
| | TANK.PLEASE NOTE, ABOVE GROUND & |
| | UNDERGROUND TANKS WITH THE CAPACITY |
| | GREATER THAN 500 GALLON SHALL BE |
| | SUBMITTED TO DERM TO THE ATTENTION OF |
| | CHIP GREEN.PLANS MAY BE SUBMITTED AT |
| | 3323 BELVEDERE RD., BUILD # 502. |
| | |
| | 5.PLEASE PROVIDE ANCHORING DETAIL. |
| | |
| | 6.PLEASE PROVIDE MANUFACTURER |
| | SUBMITTAL OF THE "PRECAST CONTRETE |
| | BASE". |
| | |