| 2006-07-21 00:00:00 | ******** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE THE VALUE FOR |
| | COMPLETE SCOPE OF WORK SHALL BE |
| | INLCUDED. PLEASE KNOW, EVEN IF ANY |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | FBC 108.3 , ADMIN SECT. |
| | PLEASE ADJUSTOR ONE WILL BE ASSESSED |
| | PER MARSHALL'S SWIFT GUIDE AS ADOPTED |
| | UNDER THE FBC. |
| | |
| | 2) NOTE: PLEASE PROVIDE SLAB INFORMATION |
| | AT THIS TIME. PLEASE KNOW, THE SIZE, TIE |
| | DOWN ETC FOR GEN AND SLAB INFORMATION IS |
| | REQUIRED AT THIS TIME BEFORE PERMIT FOR |
| | GENERATOR CAN BE ISSUED. |
| | PLEASE SEE BUIDLING REVIEW COMMENTS. |
| | 106.1.2 |
| | |
| | 3) NOTE: PLEASE CORRELATE AND CLARIFY |
| | ATS BEING INSTALLED. NO |
| | SPES/MANUFCATURES CUT SHEETS WERE |
| | SUBMITTED FOR REVIEW. PLEASE SEE A PRINT |
| | OUT FROM AN WEBSITE INDICATE AN "ONAN" |
| | YET PLANS CALL FOR GENERAC ATS WHICH |
| | WOULD CORRELATE WITH THE LISTED GENERAC |
| | GENERATOR. |
| | PLEASE CORRELATE AND SUBMIT ALL |
| | INFORMATION. |
| | PLEASE SEE MISSING WP HOUSING SPECS. |
| | PLEASE BE SURE MIN CLEARENCES ARE |
| | INDICATE FOR GEN AND PLEASE BE SURE AIC |
| | RATINGS FOR ALL EQUIPMENT IS SHOWN. |
| | 110.9,702.6,215.5,110.26,110.3,90.7 ETC |
| | |
| | 4) NOTE: PLEASE SUBMIT THE SPECS/CUT |
| | SHEET FOR FUEL TANK AND SIZE. PLEASE |
| | INDICATE GPH USEGAE AND SHOW ON PLANS. |
| | PLEASE KNOW, EVEN THOUGH THE FUEL PERMIT |
| | WILL BE SEPARATE THIS INFORMATION IS |
| | REQUIRED AT THIS TIME. PLEASE ALSO SEE |
| | MECH REVIEW AND FIRE REVIEW COMMENTS. |
| | 110.3,90.7, |
| | 106.1.2 FBC |
| | |
| | 5) NOTE: PLEASE SPECIFY THE NFPA-110 |
| | PLEASE SEE CHAPTER 27 OF THE 2004 FBC, |
| | AND 2002 110. |
| | |
| | 6) NOTE: PLEASE SHOW AND INDICATE ALL |
| | SETBACKS FOR GENERATOR AND EQUIPMENT. |
| | 106.1.2 |
| | |
| | 7) NOTE: PLEASE CLARIFY IF THE EXISTING |
| | MAIN PANEL WHERE IT APPEARS TO BE |
| | LOCATED ADJACENT TO THE NEW SE RATED ATS |
| | CONTAINS A MAIN? |
| | PLEASE ALSO PROVIDE INFORMATION BY THE |
| | WAY OF THE SPECS TO BE SUBMITTED AND |
| | PLANS THAT THE ATS CONTAINS A MANUAL |
| | MENAS OF DISCONNECT RATED FOR THE LOAD |
| | SERVICED ON THE OUTSIDE AS REQUIRED PER |
| | 230.70,230.76,230.79. |
| | PLEASE KNOW, IF THE EXISTING MAIN PANEL |
| | DOES NOT CONTAINA MCB, AND THE ATS DOES |
| | NOT DISCONNECT POWER FROM BOTH NORMAL |
| | AND EM SIDES TO A CENTER OFF POSITION, A |
| | MEANS OF DISCONNECT WILL BE REQUIRED |
| | LOCATED AT BUIDLING GROUPED WITH OUTHER |
| | MAINS. |
| | 225.31-225.39 |
| | |
| | PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL AND OTHER |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |