| 2007-06-27 09:01:35 | REVISED MECHANICAL PLANS | | | *** DENIED *** | | | 1) REVISED PLANS SHOW NO RETURN AIR GRILL SO AIR MAY | | | RETURN TO AHU. | | | | | | 2) PLANS 2ND. FLOOR SHOW 8" SUPPLY AIR DUCT GOING TO A | | | 10X10 SUPPLY AIR GRILL THEN TO A MIXING BOX, SHOULDN'T | | | IT GO TO THE MIXING BOX THEN THE 10X10 SUPPLY AIR | | | GRILL, PLEASE CORRECT IF SO. | | | | | | 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|