Plan Review Notes
Plan Review Notes For Permit 06061694
Permit Number 06061694
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-06 00:00:00****** UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE THERE ARE SOME NEW ITEMS
 FROM PREVIOUS REVIEW AND NEW COMMENTS
 DUE TO RISER BEING COMPLETELY REVISED
 FOR MAIN HOUSE ETC.
 PLEASE SEE NOTES BELOW ARE TAKEN FROM
 PREVIOUS TWO REVIEWS ALONG WITH ALL NEW
 NOTES ADDED TO BOTTOM OF OLD NOTES.
  
  
 1) NOTE: OK, HOWEVER NOW SUBMITTING
 COMPLETED PLANS, HOWEVER THERE ARE MANY
 ITEMS NOT CODE COMPLIANT, SEE NEW NOTES.
  
 ** PREVIOUS REVIEW #2**
 NO, PLEASE SEE PANEL AT MAIN
 HOUSE MAY NOT BE USED CARRYING BRANCH
 CIRCUITS TO CABANA. PLEASE SEE MISSING
 PANEL, GROUNDING, DISCONNECTING MEANS
 ETC AS PREVIOUSLY NOTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE COMPLETE PLANS FOR
 REVIEW. PLEASE SEE NO INFORMATION WAS
 SUBMITTED FOR NEW REQUIRED PANEL, MEANS
 OF DISCONNECT, PANEL SCHEDULE, GROUNDING
 ETC AT THE DETACHED BLDG.
 PLEASE SEE 225.31-225.39, 250.32,250.50,
 215.5, 240.21 ETC
  
 2) NOTE: NO, PLEASE SEE LOAD
 CALCULAITONS SUBMITTED ARE NOT CODE
 COMPLIANT PER NEC AND PLEASE SEE NEW
 COMMENTS BASED ON REVISED PLANS.
  
 ** PREVIOUS REVIEW #2 NOTE **
 NO, PLEASE SEE LOAD
 CALCULATIONS DO NOT MEET CODE PER
 220.31B. PLEASE SEE PANEL SCHEDULE IS
 NOT COMPLETE WITH ALL INFORMATION AS
 REQUIRED. ONLY ONE CIRCUIT BEING SHOWN
 FOR ALL LTS AND GEN PURPOSE RECEPTS,
 MISSING ARC FAULT PROTECTION AS UPSTAIRS
 IS AN ADAPTBALE SLEEPING RM.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE COMPLETE AND CORRELATE
 ALL CIRCUITING ON PLANS WITH PANEL
 SCHEDULE AND COMPLETE LOAD CALCULATIONS.
 PLEASE SEE PLANS SHOW ITEMS WHICH ARE
 NOT FIGURED OR SHOWN ON PANEL
 SCHEDULE/LOAD CALCS.
 PLEASE KNOW, ALL CIRCUITS SHALL BE
 SPECIFIC TO ROOMS AND AREAS IN
 STRUCTURE.
 PLEASE SEE MORE THEN ONE SM APPL CIRCUIT
 IS INDICATE HOWEVER ONLY TWO ARE
 FIGURED.
 PLEASE SEE NO TANKLESS WH IS SHOWN ON
 PANEL SCHEDULE OR FIGURED IN LOAD
 CALCULATIONS.
 PLEASE SEE ONLY ONE A/C SYSTEM IS
 FIGURED IN LOADS.
 PLEASE SEE NO LOADS FROM EXISTING
 DWELLING IS SHOWN OR FIGURED IN WITH NEW
 LOADS.
 PLEASE LABEL ALL RMS/AREAS ON PLANS.
 240.4,310.16,220.31B,408.4
 FBC 106.1.2, 106.1.3 ADMIN SECT.
  
 3) NOTE: OK.
  
 4) NOTE: NO, SOME INFORMATION SUBMITTED
 HOWEVER SEE NEW NOTES FOR DISCONNECTING
 MEANS ETC DUE TO SPECS BEING SUBMITTED.
 PLEASE SEE 210.63,210.70
  
 ** PREVIOUS REVIEW #2 NOTE **
 NO, NO CORRECTIONS MADE, AND
 ITEMS NOT SHOWN AS REQUIRED PER CODE.
 A NOTE WAS ADDED TO SEE LOCATIONS OF
 CU'S ON SURVEY, HOWEVER THE ELECTRICAL
 PLANS ARE REQUIRED TO CONTAIN THE
 ELECTRICAL INFORMATION AS REQUIRED.
 DISCONNECTS, RECEPTS FOR CU'S ETC,
 MIN CLEARENCES ETC.
 PLEASE SUBMIT THE SPECS/MANUFACTURES CUT
 SHEETS FOR THE TANKLESS WATER HEATER
 UNIT. PLEASE BE SURE THE SHEETS CONTAIN
 THE LISTING FROM A NRTL.
 110.26,210.63,210.8,440.11,240.24,422.31
 ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
  
 PLEASE SEE 110.26, 240.24,
 440.11, 422.31 ETCFOR MIN DISCONNECTS
 REQUIRED FOR AHU/ TKLESS WH. PLEASE SEE
 AREAS FOR MIN CLEARENCES, AND STORAGE
 AREAS WHERE EASILY IGNITIBLE MATERIALS
 AND OCP.
  
 5) NOTE: OK, HOWEVER SEE NEW NOTES.
  
  
 ** NEW NOTES 2ND REVIEW **
  
 6) NOTE:NO, PLEASE SEE DUE TO REPEAT
 COMMENTS A FEE HAS BEEN ASSESSED TO THE
 DESIGN TEAM AS REQUIRED PER FS
 553.80(2)(B). THE AMOUNT OF $1300.24
 MUST BE PAID BEFORE NEXT RESUB OF PLANS.
 IT IS THE SUGGESTION OF THIS OFFICE AS
 ONE SET OF PLANS ARE BEING RETAINED ,
 THAT A MEETING BE HELD WITH ALL RELEVANT
 PARTIES TO GO OVER PLANS ETC. PLEASE
 KNOW, IF PLANS COME BACK FOR A FORTH
 REVIEW AND "ANY" OF THE SAME COMMENTS
 ARE NOT ADDRESSED, THE FEE IS ASSESSED
 ONCE MORE. PLANS MAY NOW ALL BE TURNED
 INTO THE STATE BOARD OF ARCHIECTS FOR
 REVIEW.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT CODE COMPLIANT
 COMMENTS FOR DESIGN PROFESSIONAL.
 PLEASEKNOW, ONE COPY OF EACH SET OF
 ELECTRICAL IS BEING RETAINED. PLEASE
 KNOW, IT MAY BE REQUIRED BY THIS OFFICE
 THAT PLANS BE DONE BY AN ARCHITECT,
 ENGINEER OR PERSON LICENSED UNDER FS
 489.
  
 7) NOTE: OK.
  
 ***********************************
 THIS FYI WAS PLACED ON PREVIOUS REVIEW.
  
 ** PLEASE KNOW, DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, THERE MAY BE
 FUTURE COMMENTS AS PLANS WILL CHANGE.
  
 ************************************
  
  
  
 *** NEW NOTES FOR 3RD REVIEW DUE TO NEW
 PLANS BEING SUBMITTED.
  
 1) NOTE: PLEASE SEE RISER, PLEASE
 CORRELATE AS THIS RISER IS COMPLETELY
 DIFFERENT FROM THEMAIN HOUSE PLANS AND
 NOW DOES NOT MEET MANY ITEMS CODE
 RELATED..
  
 A) PLEASE SEE RISER NOW SHOWS A NEW 150A
 PANEL "B", WHICH IS BEING FED FROM
 3-#3'S WHICH ARE ONLY RATED AT 100A'S.
 PLEASE PREVIOUS REVISED RISER SHOWS A
 125A PANEL "B" WITH A 100A MCB AND NOW
 SERVICE IS BEING INCREASED AND NO
 CONSIDERATION HAS BEEN TAKEN TO THE
 INCREASE FOR SERVICE ENTRANCE CONDUCTORS
 FOR NEW 150A MCB PANEL AND INCREASED
 SERVICE.
  
 B) PLEASE SEE 250.66, 310.15B6, 310.16,
 AS THE SEC'S TOTAL WILL NOW BE INCREASED
 ,T HE GROUNDING ELECTRODE CONDUCTOR WILL
 NOW BE REQUIRED TO MEET 250.66. THE
 PREVIOUS #2, IS NO LONGER LARGE ENOUGH.
  
 C) PLEASE SEE RISER SHOWS 3-3/0'S AND
 1-#6 IN AN 1 1/4" CONDUIT FROM PANEL "B"
 TO NEW PANEL "C" (CABANAN PANEL).
 PLEASE SEE THE FIRST ITEM IS THAT PANEL
 "B" SHOWS A 2-POLE 70A BRKR FEEDING NEW
 PANEL "C", 3/0'S WILL NOT FIT INTO A 70A
 BREAKER.
 PLEASE SEE THE SECOND ITEM IS THAT PANEL
 "B" SHOWS #4'S WHICH IS COMPLETELY
 DIFFERENT FROM RISER WHICH SHOWS 3/0'S?
 THE THIRD ISSUE IS THAT 3-3/0'S AND 1-#6
 WILL NOT FIT INTO 1 1/4" CONDUIT AS
 SHOWN ON RISER. PLEASE SEE TABLES IN
 CHAPTER 9.
 PLEASE SEE , 240.4,310.15B6,310.16,
 CHAPTE 9, 215.2, ETC ETC
  
 2) NOTE; PLEASE SEE NOW THE SPECS FOR
 THE NEW TANKLESS WATER HEATER IS BEING
 SUBMITTED FOR THE FIRST TIME. PLEASE SEE
 THE UNIT SUBMITTED ITSELF AT 17.25KW
 EXCEEDS THE PROPOSED 70A FEED TO THE
 PANEL "C". PLEASE SEE THE LOADS ON PANEL
 "C" ARE NOT CORRECT AS THEY DO NOT ADD
 UP.
 THE TKLESS WH IS OVER 70A'S ALONE !!!
 PLEASE SEE THE * ON SPEC SHEETS WHICH
 EVEN STATES A MIN SERVICE FOR THIS SIZE
 UNIT FOR A DWELLING. THE MIN OCP FOR THE
 UNIT IS 80A'S, WHICH IS STATED ON SPECS.
 PLEASE KNOW, IF THE PANEL IS FEEDING
 THIS UNIT IS OUTSIDE,WITH TWO-2-POLE
 40'S, THEN PLANS WOULD SHOW MORE THAN
 ONE DISCONNECT INSIDE FEEDING THIS UNIT.
 422.11, 110.26, 422.31, 422.30 ETC.
 110.3,90.7.
  
 3) NOTE: PLEASE SEE 210.52 AS RAILING IS
 CONSIDERED WALL SPACE AND WALL SPACE ON
 2ND FLR IS MISSING ONE RECEPT. IF THIS
 WAS THE ONLY ITEM IT WOULD BE REDLINED.
  
  
 4) NOTE: PLEASE KNOW, IF THIS RISER HAS
 INDEED CHANGED THIS MUCH AS SHOWN FOR
 THE MAIN HOUSE SERVICE FROM THE LAST
 REVISION WHICH WAS SUBMITTED, PLEASE
 SUBMIT REVISED PLANS FOR MAIN HOUSE, AS
 THE WILL GREATLY AFFECT THE ELECTRICAL
 INSPECTIONS FOR MAIN HOUSE.
  
  
 3) NOTE: PLEASE SEE PANEL"C"/ CABANA
 PANEL ON RISER IS BEING SHOWN AS A 100A
 MCB PANEL, YET THE PLANS ALSO SHOW A
 DISCONNECT OUTSIDE WHICH IS NOT ON
 RISER??
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  