Plan Review Notes
Plan Review Notes For Permit 06061694
Permit Number 06061694
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-08 00:00:00****** UNSAT 2ND REVIEW ******
  
 ** PLEASE SEE MOST ITEMS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED AND
 PLANSARE NOT CODE COMPLIANT. PLEASE
 SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW NOTES ALONG WITH NEW
 NOTES ADDED.
  
  
 1) NOTE: NO, PLEASE SEE PANEL AT MAIN
 HOUSE MAY NOT BE USED CARRYING BRANCH
 CIRCUITS TO CABANA. PLEASE SEE MISSING
 PANEL, GROUNDING, DISCONNECTING MEANS
 ETC AS PREVIOUSLY NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PLANS FOR
 REVIEW. PLEASE SEE NO INFORMATION WAS
 SUBMITTED FOR NEW REQUIRED PANEL, MEANS
 OF DISCONNECT, PANEL SCHEDULE, GROUNDING
 ETC AT THE DETACHED BLDG.
 PLEASE SEE 225.31-225.39, 250.32,250.50,
 215.5, 240.21 ETC
  
 2) NOTE:NO, PLEASE SEE LOAD
 CALCULATIONS DO NOT MEET CODE PER
 220.31B. PLEASE SEE PANEL SCHEDULE IS
 NOT COMPLETE WITH ALL INFORMATION AS
 REQUIRED. ONLY ONE CIRCUIT BEING SHOWN
 FOR ALL LTS AND GEN PURPOSE RECEPTS,
 MISSING ARC FAULT PROTECTION AS UPSTAIRS
 IS AN ADAPTBALE SLEEPING RM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE AND CORRELATE
 ALL CIRCUITING ON PLANS WITH PANEL
 SCHEDULE AND COMPLETE LOAD CALCULATIONS.
 PLEASE SEE PLANS SHOW ITEMS WHICH ARE
 NOT FIGURED OR SHOWN ON PANEL
 SCHEDULE/LOAD CALCS.
 PLEASE KNOW, ALL CIRCUITS SHALL BE
 SPECIFIC TO ROOMS AND AREAS IN
 STRUCTURE.
 PLEASE SEE MORE THEN ONE SM APPL CIRCUIT
 IS INDICATE HOWEVER ONLY TWO ARE
 FIGURED.
 PLEASE SEE NO TANKLESS WH IS SHOWN ON
 PANEL SCHEDULE OR FIGURED IN LOAD
 CALCULATIONS.
 PLEASE SEE ONLY ONE A/C SYSTEM IS
 FIGURED IN LOADS.
 PLEASE SEE NO LOADS FROM EXISTING
 DWELLING IS SHOWN OR FIGURED IN WITH NEW
 LOADS.
 PLEASE LABEL ALL RMS/AREAS ON PLANS.
 240.4,310.16,220.31B,408.4
 FBC 106.1.2, 106.1.3 ADMIN SECT.
  
 3) NOTE: OK.
  
 4) NOTE: NO, NO CORRECTIONS MADE, AND
 ITEMS NOT SHOWN AS REQUIRED PER CODE.
 A NOTE WAS ADDED TO SEE LOCATIONS OF
 CU'S ON SURVEY, HOWEVER THE ELECTRICAL
 PLANS ARE REQUIRED TO CONTAIN THE
 ELECTRICAL INFORMATION AS REQUIRED.
 DISCONNECTS, RECEPTS FOR CU'S ETC,
 MIN CLEARENCES ETC.
 PLEASE SUBMIT THE SPECS/MANUFACTURES CUT
 SHEETS FOR THE TANKLESS WATER HEATER
 UNIT. PLEASE BE SURE THE SHEETS CONTAIN
 THE LISTING FROM A NRTL.
 110.26,210.63,210.8,440.11,240.24,422.31
 ETC.
  
 ** PREVIOUS REVIEW NOTE**
  
 PLEASE SEE 110.26, 240.24,
 440.11, 422.31 ETCFOR MIN DISCONNECTS
 REQUIRED FOR AHU/ TKLESS WH. PLEASE SEE
 AREAS FOR MIN CLEARENCES, AND STORAGE
 AREAS WHERE EASILY IGNITIBLE MATERIALS
 AND OCP.
  
 5) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTES **
 PLEASE SEE PLANS DO NOT CONTAIN
 ANY PRINTED NAME AND SIGNATURE OF THE
 PERSON TAKING RESPONSIBILITY FOR PLANS
 AND DESIGN.
 **WHEN PLANS ARE REQUIRED TO BE DONE BY
 AN ARCHITECT OR ENGINEER PLEASE SEE FS
 481/471
 FBC 106.1.2 ADMIN SECT.
  
 ** NEW NOTES **
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT CODE COMPLIANT
 COMMENTS FOR DESIGN PROFESSIONAL.
 PLEASEKNOW, ONE COPY OF EACH SET OF
 ELECTRICAL IS BEING RETAINED. PLEASE
 KNOW, IT MAY BE REQUIRED BY THIS OFFICE
 THAT PLANS BE DONE BY AN ARCHITECT,
 ENGINEER OR PERSON LICENSED UNDER FS
 489.
  
 7) NOTE: PLEASE SEE SURVEY IS REQUIRED
 TO CONTAIN AN ORIGINAL SIGNATURE PER FS
 472.025. PLEASE SEE FAC 61G17.
 STATEMENT ON SURVEY MENTIONS "NOT VALID
 WITHOUT SIGNATURE AND RAISED SEAL". A
 RIASED SEAL OVER A PHOTO-COPIED
 SIGNATURE DOES NOT MAKE THIS VALID.
 THIS COMMENT IS NOT FOR "ON TARGET"
 DESIGNS.
  
 ** PLEASE KNOW, DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, THERE MAY BE
 FUTURE COMMENTS AS PLANS WILL CHANGE.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOUDL BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  