| 2006-09-08 00:00:00 | ****** UNSAT 2ND REVIEW ****** |
| | |
| | ** PLEASE SEE MOST ITEMS FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED AND |
| | PLANSARE NOT CODE COMPLIANT. PLEASE |
| | SEE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW NOTES ALONG WITH NEW |
| | NOTES ADDED. |
| | |
| | |
| | 1) NOTE: NO, PLEASE SEE PANEL AT MAIN |
| | HOUSE MAY NOT BE USED CARRYING BRANCH |
| | CIRCUITS TO CABANA. PLEASE SEE MISSING |
| | PANEL, GROUNDING, DISCONNECTING MEANS |
| | ETC AS PREVIOUSLY NOTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE PLANS FOR |
| | REVIEW. PLEASE SEE NO INFORMATION WAS |
| | SUBMITTED FOR NEW REQUIRED PANEL, MEANS |
| | OF DISCONNECT, PANEL SCHEDULE, GROUNDING |
| | ETC AT THE DETACHED BLDG. |
| | PLEASE SEE 225.31-225.39, 250.32,250.50, |
| | 215.5, 240.21 ETC |
| | |
| | 2) NOTE:NO, PLEASE SEE LOAD |
| | CALCULATIONS DO NOT MEET CODE PER |
| | 220.31B. PLEASE SEE PANEL SCHEDULE IS |
| | NOT COMPLETE WITH ALL INFORMATION AS |
| | REQUIRED. ONLY ONE CIRCUIT BEING SHOWN |
| | FOR ALL LTS AND GEN PURPOSE RECEPTS, |
| | MISSING ARC FAULT PROTECTION AS UPSTAIRS |
| | IS AN ADAPTBALE SLEEPING RM. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE AND CORRELATE |
| | ALL CIRCUITING ON PLANS WITH PANEL |
| | SCHEDULE AND COMPLETE LOAD CALCULATIONS. |
| | PLEASE SEE PLANS SHOW ITEMS WHICH ARE |
| | NOT FIGURED OR SHOWN ON PANEL |
| | SCHEDULE/LOAD CALCS. |
| | PLEASE KNOW, ALL CIRCUITS SHALL BE |
| | SPECIFIC TO ROOMS AND AREAS IN |
| | STRUCTURE. |
| | PLEASE SEE MORE THEN ONE SM APPL CIRCUIT |
| | IS INDICATE HOWEVER ONLY TWO ARE |
| | FIGURED. |
| | PLEASE SEE NO TANKLESS WH IS SHOWN ON |
| | PANEL SCHEDULE OR FIGURED IN LOAD |
| | CALCULATIONS. |
| | PLEASE SEE ONLY ONE A/C SYSTEM IS |
| | FIGURED IN LOADS. |
| | PLEASE SEE NO LOADS FROM EXISTING |
| | DWELLING IS SHOWN OR FIGURED IN WITH NEW |
| | LOADS. |
| | PLEASE LABEL ALL RMS/AREAS ON PLANS. |
| | 240.4,310.16,220.31B,408.4 |
| | FBC 106.1.2, 106.1.3 ADMIN SECT. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: NO, NO CORRECTIONS MADE, AND |
| | ITEMS NOT SHOWN AS REQUIRED PER CODE. |
| | A NOTE WAS ADDED TO SEE LOCATIONS OF |
| | CU'S ON SURVEY, HOWEVER THE ELECTRICAL |
| | PLANS ARE REQUIRED TO CONTAIN THE |
| | ELECTRICAL INFORMATION AS REQUIRED. |
| | DISCONNECTS, RECEPTS FOR CU'S ETC, |
| | MIN CLEARENCES ETC. |
| | PLEASE SUBMIT THE SPECS/MANUFACTURES CUT |
| | SHEETS FOR THE TANKLESS WATER HEATER |
| | UNIT. PLEASE BE SURE THE SHEETS CONTAIN |
| | THE LISTING FROM A NRTL. |
| | 110.26,210.63,210.8,440.11,240.24,422.31 |
| | ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | |
| | PLEASE SEE 110.26, 240.24, |
| | 440.11, 422.31 ETCFOR MIN DISCONNECTS |
| | REQUIRED FOR AHU/ TKLESS WH. PLEASE SEE |
| | AREAS FOR MIN CLEARENCES, AND STORAGE |
| | AREAS WHERE EASILY IGNITIBLE MATERIALS |
| | AND OCP. |
| | |
| | 5) NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTES ** |
| | PLEASE SEE PLANS DO NOT CONTAIN |
| | ANY PRINTED NAME AND SIGNATURE OF THE |
| | PERSON TAKING RESPONSIBILITY FOR PLANS |
| | AND DESIGN. |
| | **WHEN PLANS ARE REQUIRED TO BE DONE BY |
| | AN ARCHITECT OR ENGINEER PLEASE SEE FS |
| | 481/471 |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | ** NEW NOTES ** |
| | |
| | 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT CODE COMPLIANT |
| | COMMENTS FOR DESIGN PROFESSIONAL. |
| | PLEASEKNOW, ONE COPY OF EACH SET OF |
| | ELECTRICAL IS BEING RETAINED. PLEASE |
| | KNOW, IT MAY BE REQUIRED BY THIS OFFICE |
| | THAT PLANS BE DONE BY AN ARCHITECT, |
| | ENGINEER OR PERSON LICENSED UNDER FS |
| | 489. |
| | |
| | 7) NOTE: PLEASE SEE SURVEY IS REQUIRED |
| | TO CONTAIN AN ORIGINAL SIGNATURE PER FS |
| | 472.025. PLEASE SEE FAC 61G17. |
| | STATEMENT ON SURVEY MENTIONS "NOT VALID |
| | WITHOUT SIGNATURE AND RAISED SEAL". A |
| | RIASED SEAL OVER A PHOTO-COPIED |
| | SIGNATURE DOES NOT MAKE THIS VALID. |
| | THIS COMMENT IS NOT FOR "ON TARGET" |
| | DESIGNS. |
| | |
| | ** PLEASE KNOW, DUE TO PLANS NOT BEING |
| | COMPLETE AT THIS TIME, THERE MAY BE |
| | FUTURE COMMENTS AS PLANS WILL CHANGE. |
| | |
| | ** PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF THE OLD/VOIDED REMOVED |
| | SHEETS SHOUDL BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |