Plan Review Notes
Plan Review Notes For Permit 06061694
Permit Number 06061694
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-19 00:00:00****** UNSAT ******
  
 1) NOTE: PLEASE COMPLETE PLANS FOR
 REVIEW. PLEASE SEE NO INFORMATION WAS
 SUBMITTED FOR NEW REQUIRED PANEL, MEANS
 OF DISCONNECT, PANEL SCHEDULE, GROUNDING
 ETC AT THE DETACHED BLDG.
 PLEASE SEE 225.31-225.39, 250.32,250.50,
 215.5, 240.21 ETC
  
 2) NOTE: PLEASE COMPLETE AND CORRELATE
 ALL CIRCUITING ON PLANS WITH PANEL
 SCHEDULE AND COMPLETE LOAD CALCULATIONS.
 PLEASE SEE PLANS SHOW ITEMS WHICH ARE
 NOT FIGURED OR SHOWN ON PANEL
 SCHEDULE/LOAD CALCS.
 PLEASE KNOW, ALL CIRCUITS SHALL BE
 SPECIFIC TO ROOMS AND AREAS IN
 STRUCTURE.
 PLEASE SEE MORE THEN ONE SM APPL CIRCUIT
 IS INDICATE HOWEVER ONLY TWO ARE
 FIGURED.
 PLEASE SEE NO TANKLESS WH IS SHOWN ON
 PANEL SCHEDULE OR FIGAURED IN LOAD
 CALCULATIONS.
 PLEASE SEE ONLY ONE A/C SYSTEM IS
 FIGURED IN LOADS.
 PLEASE SEE NO LOADS FROM EXISTING
 DWELLING IS SHOWN OR FIGURED IN WITH NEW
 LOADS.
 PLEASE LABEL ALL RMS/AREAS ON PLANS.
 240.4,310.16,220.31B,408.4
 FBC 106.1.2, 106.1.3 ADMIN SECT.
  
 3) NOTE: PLEASE SEE MISSING DEDICATED
 BATH(S) CIRCUITS.
 210.52D, 210.11C3
  
 4) NOTE: PLEASE SEE 110.26, 240.24,
 440.11, 422.31 ETCFOR MIN DISCONNECTS
 REQUIRED FOR AHU/ TKLESS WH. PLEASE SEE
 AREAS FOR MIN CLEARENCES, AND STORAGE
 AREAS WHERE EASILY IGNITIBLE MATERIALS
 AND OCP.
  
 5) NOTE: PLEASE SEE PLANS DO NOT CONTAIN
 ANY PRINTED NAME AND SIGNATURE OF THE
 PERSON TAKING RESPONSIBILITY FOR PLANS
 AND DESIGN.
 **WHEN PLANS ARE REQUIRED TO BE DONE BY
 AN ARCHITECT OR ENGINEER PLEASE SEE FS
 481/471
 FBC 106.1.2 ADMIN SECT.
  
 ** PLEASE KNOW, DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, THERE MAY BE
 FUTURE COMMENTS AS PLANS WILL CHANGE.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOUDL BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved