| Date |
Text |
| 2006-07-19 00:00:00 | ****** UNSAT ****** |
| | |
| | 1) NOTE: PLEASE COMPLETE PLANS FOR |
| | REVIEW. PLEASE SEE NO INFORMATION WAS |
| | SUBMITTED FOR NEW REQUIRED PANEL, MEANS |
| | OF DISCONNECT, PANEL SCHEDULE, GROUNDING |
| | ETC AT THE DETACHED BLDG. |
| | PLEASE SEE 225.31-225.39, 250.32,250.50, |
| | 215.5, 240.21 ETC |
| | |
| | 2) NOTE: PLEASE COMPLETE AND CORRELATE |
| | ALL CIRCUITING ON PLANS WITH PANEL |
| | SCHEDULE AND COMPLETE LOAD CALCULATIONS. |
| | PLEASE SEE PLANS SHOW ITEMS WHICH ARE |
| | NOT FIGURED OR SHOWN ON PANEL |
| | SCHEDULE/LOAD CALCS. |
| | PLEASE KNOW, ALL CIRCUITS SHALL BE |
| | SPECIFIC TO ROOMS AND AREAS IN |
| | STRUCTURE. |
| | PLEASE SEE MORE THEN ONE SM APPL CIRCUIT |
| | IS INDICATE HOWEVER ONLY TWO ARE |
| | FIGURED. |
| | PLEASE SEE NO TANKLESS WH IS SHOWN ON |
| | PANEL SCHEDULE OR FIGAURED IN LOAD |
| | CALCULATIONS. |
| | PLEASE SEE ONLY ONE A/C SYSTEM IS |
| | FIGURED IN LOADS. |
| | PLEASE SEE NO LOADS FROM EXISTING |
| | DWELLING IS SHOWN OR FIGURED IN WITH NEW |
| | LOADS. |
| | PLEASE LABEL ALL RMS/AREAS ON PLANS. |
| | 240.4,310.16,220.31B,408.4 |
| | FBC 106.1.2, 106.1.3 ADMIN SECT. |
| | |
| | 3) NOTE: PLEASE SEE MISSING DEDICATED |
| | BATH(S) CIRCUITS. |
| | 210.52D, 210.11C3 |
| | |
| | 4) NOTE: PLEASE SEE 110.26, 240.24, |
| | 440.11, 422.31 ETCFOR MIN DISCONNECTS |
| | REQUIRED FOR AHU/ TKLESS WH. PLEASE SEE |
| | AREAS FOR MIN CLEARENCES, AND STORAGE |
| | AREAS WHERE EASILY IGNITIBLE MATERIALS |
| | AND OCP. |
| | |
| | 5) NOTE: PLEASE SEE PLANS DO NOT CONTAIN |
| | ANY PRINTED NAME AND SIGNATURE OF THE |
| | PERSON TAKING RESPONSIBILITY FOR PLANS |
| | AND DESIGN. |
| | **WHEN PLANS ARE REQUIRED TO BE DONE BY |
| | AN ARCHITECT OR ENGINEER PLEASE SEE FS |
| | 481/471 |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | ** PLEASE KNOW, DUE TO PLANS NOT BEING |
| | COMPLETE AT THIS TIME, THERE MAY BE |
| | FUTURE COMMENTS AS PLANS WILL CHANGE. |
| | |
| | ** PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF THE OLD/VOIDED REMOVED |
| | SHEETS SHOUDL BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |