2006-10-01 00:00:00IN ELEC
 ** UNSAT 3RD REVIEW **
  
 1) NOTE: PLEASE SEE THE OVER-RIDE
 DEVICES SHALL ALL BE SHOWN ON PLANS
 WHICH OVER RIDE "SYSTEM". PLEASE SEE
 INGRESS /EGRESS AREAS WHICH ONE "S" IS
 SHOWN HOWEVER PLANS DO NOT DELINEATE THE
 DEVICE BEING USED FOR OVER RIDE."TYPE"?.
 PLEASE SEE ALSO ENTRANCE "S' WHICH IS
 ALSO REQUIRED OVER-RIDE SYSTEM. SAME
 NOTE.
 PLEASE KNOW AS STATED ON PREVIOUS REVIEW
 THE TYPE OF DEVICES MUST STATE THE MAX
 TIME ON OVER-RIDE DEPENDING ON DEVICE
 BEING CHOSEN.
 MOTION/OCUPANT SENSOR TYPE (30MINS MAX),
 TIMER TYPE 4HRS MAX).
  
 2) NOTE: PLEASE SEE LPD'S AS PREVIOUSLY
 REQUESTED CAN NOT BE VERIFIED AS THE
 FIXTURE SCHEDULE DOES NOT PROVIDE THE
 FIXTURE WATTAGE, TYPE ETC.
 IF DOING A SPACE BY SPACE METHOD ,
 PROVIDE BREAKDOWN OF AREAS.
 NOT ENOUGH INFORMATION TO VERIFY. MAX
 LPD'S.
 13-415.2, 13-415.2.ABC.1.
  
 3) NOTE: PLEASE SEE ATTACHED NOTICE
 GIVEN WITH RESPECT TO DESIGN
 PROFESSIONALS AND FS 553.80(2)(B).
 THIS IS BEING GIVEN AS A NOTICE AT THIS
 TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  