| 2006-10-01 00:00:00 | IN ELEC |
| | ** UNSAT 3RD REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE OVER-RIDE |
| | DEVICES SHALL ALL BE SHOWN ON PLANS |
| | WHICH OVER RIDE "SYSTEM". PLEASE SEE |
| | INGRESS /EGRESS AREAS WHICH ONE "S" IS |
| | SHOWN HOWEVER PLANS DO NOT DELINEATE THE |
| | DEVICE BEING USED FOR OVER RIDE."TYPE"?. |
| | PLEASE SEE ALSO ENTRANCE "S' WHICH IS |
| | ALSO REQUIRED OVER-RIDE SYSTEM. SAME |
| | NOTE. |
| | PLEASE KNOW AS STATED ON PREVIOUS REVIEW |
| | THE TYPE OF DEVICES MUST STATE THE MAX |
| | TIME ON OVER-RIDE DEPENDING ON DEVICE |
| | BEING CHOSEN. |
| | MOTION/OCUPANT SENSOR TYPE (30MINS MAX), |
| | TIMER TYPE 4HRS MAX). |
| | |
| | 2) NOTE: PLEASE SEE LPD'S AS PREVIOUSLY |
| | REQUESTED CAN NOT BE VERIFIED AS THE |
| | FIXTURE SCHEDULE DOES NOT PROVIDE THE |
| | FIXTURE WATTAGE, TYPE ETC. |
| | IF DOING A SPACE BY SPACE METHOD , |
| | PROVIDE BREAKDOWN OF AREAS. |
| | NOT ENOUGH INFORMATION TO VERIFY. MAX |
| | LPD'S. |
| | 13-415.2, 13-415.2.ABC.1. |
| | |
| | 3) NOTE: PLEASE SEE ATTACHED NOTICE |
| | GIVEN WITH RESPECT TO DESIGN |
| | PROFESSIONALS AND FS 553.80(2)(B). |
| | THIS IS BEING GIVEN AS A NOTICE AT THIS |
| | TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |