| 2006-08-24 00:00:00 | ** UNSAT ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM FIRST |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE ONE NEW COMMENT. |
| | NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW AS NOTED. |
| | |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: NO, PLEASE SEE TIME CLOCK, |
| | SCHEDULING, LOCATION IS NOT SHOWN. |
| | PLEASE SEE MISSING OVER RIDES FOR TC AND |
| | FOR SEPARATE SPACES. |
| | PLEASE SEE MISSING DEVICES TYPES, ETC. |
| | PLEASE SEE MISSING LPD FOR MAX WATTAGE |
| | PERMITTED AND DESIGN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC CHAPTER 13 |
| | 13-415.1.ABC.1.1, .1.2, AND .1.3 FOR |
| | LIGHTING CONTROLS, SCHEDULING, |
| | OVER-RIDES DEVICES AND LOCATIONS. |
| | PLEASE ALSO INDICATE THE TYPE OF OVER |
| | RIDE DEVICE(S) ALONG WITH MAX TIME OF |
| | 4HRS PERMITTED FOR TIMER TYPE DEVICES |
| | AND 30 MINS FOR OCC SENSOR, TYPES. |
| | PLEASE PROVIDE LPD FOR SPACE. |
| | 13-415.2.ABC.1, 415.2.C.1, 415.2.B.1 |
| | |
| | 4) NOTE:OK, HOWEVER PLEASE BE SURE TO |
| | DO THE SAME WHEN CHNAGING OUT PLANS FOR |
| | NEW SHEETS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | **IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND BEFORE |
| | PLANS ARE RESUBMITTED, PLEASE COMPLETELY |
| | REVMOVE ALL OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF THE OLD/VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE ONLY. |
| | ** PLEASE KNOW, THIS WILL HELP IN |
| | EXPEDITING THE PROJECT AND AVOID ANY |
| | POSSIBLE DELAYS. |
| | |
| | 5) NOTE: NO, PLEASE SEE ONLY ONE OF THE |
| | BELOW ARE STATED ON THE COVER SHEET. |
| | PLEASE BE SURE DESIGN CODES ARE ON |
| | ELECTRICAL PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, ALL THE CURRENT |
| | ADOPTED CODES AS FOLLOWS SHALL BE |
| | REFERENCED ON PLANS. |
| | PLANS STATE LATEST ADOPTED ETC. |
| | PLEASE PROVIDE THE FOLLOWING AT A MIN, |
| | 2004 FBC, 2002 NFPA-70(NEC), 2002 |
| | NFPA-72, 2003 NFPA-101. |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES. |
| | |
| | ** NEW NOTE ** |
| | |
| | 6) NOTE: PLEASE VERIFY NEW OR EXISTING |
| | SHOW WINDOW RECEPTS LOCATIONS. |
| | PLEASE SEE A NOTE ON PLANS MENTIONS THE |
| | SHOW WINDOW RECEPTS BEING CONTROLLED, |
| | HOWEVER NO RECEPTS SHOWN ON PLANS AND NO |
| | CIRCUITS LISTED ON PANEL SCHEDULE. |
| | 210.62, 220.12 |
| | |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |