2006-07-08 00:00:00DENIED;
 1.SUBMIT SPECIFICATION SHEET FOR
 PEDICURE CHAIRS AND ADD A DETAIL SHOWING
 HOW THE CHAIRS WILL BE INSTALLED.
 2.SHOW BACKFLOW PREVENTOR ON PLANS WITH
 DETAIL OF AIR GAP DRAIN AND POINT OF
 TERMINATION.
 3.HANDICAP DRINKING FOUNTAIN IS REQUIRED
 TO HAVE A CUP DISPENSOR FOR PEOPLE WITH
 BAD BACKS SEC.11-4.1.3(10).
 4.PEDICURE CHAIR'S SANITARY BRANCH
 DRAINS ARE NOT VENTED.
 5.SHOW ON DRAWINGS COMPLIANCE TO
 FBC-2004 PLUMBING TABLE 403.1 2(B) LIST
 EMPLOYEES AND CUSTOMERS.
 6.SANITARY ISOMETRIC; AUTOMATIC CLOTHES
 WASHER BRANCH DRAIN IS REQUIRED TO BE 3"
 SEC.406.3.
 7.WATER HEATER DETAIL; SHOW LOCATION AND
 TERMINATION OF FUNNEL, AND PAN DRAINS.
 8.SHOW ON WATER HEATER DETAIL THE
 LOCATION OF THE EXPANSION TANK, ON COLD
 WATER SIDE AFTER THE W/H SHUTOFF VALVE.
 PLUMBING PLAN REVIEW BY;