| Plan Review Notes For Permit 06061662 |
| Permit Number |
06061662 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-11 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3. GASOLINE POWERED DEMOLITION EQUIPMENT | | | SHALL NOT BE USED WITHOUT ADEQUATE | | | VENTILATION. CARBON MONOXIDE WHICH IS | | | COLORLESS, ODORLESS, AND TASTELESS CAN | | | BE PRODUCED AND CAUSE SERIOUS ILLNESS OR | | | DEATH. | | | | | | 4. WHY IS THERE AN EXIT SIGN IN THE REAR | | | OF THE SPACE WHEN THERE APPEARS TO BE NO | | | REAR EXIT DOOR. PLEASE REVISE PLANS AS | | | NECESSARY. | | | | | | 5. PLANS NEED TO ILLUSTRATE TENANT | | | SEPARATION WALLS. | | | | | | 6. WHAT TYPE OF LIGHT BULBS ARE PLANNED | | | TO BE USED IN THE MANICURE AREA. | | | FLAMMABLE AND COMBUSTIBLE VAPORS WILL BE | | | PRESENT DIRECTLY UNDER LIGHT FIXTURE | | | BULBS. PROBLEMS HAVE OCCURRED IN THE | | | PAST IN THESE PARTICULAR AREAS WHERE | | | SIGNIFICANT CONCENTRATION OF THESE | | | VAPORS ARE PRESENT. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|