Date Text
2006-07-15 00:00:00********** UNSAT **********
  
 1) NOTE: PLEASE VERIFY "TAPPED"
 CONDUCTORS FROM GUTTER TO PANEL AND A/C
 DISCONNECT.
 240.21,310.16, 215.5
  
 2) NOTE: PLEASE SEE RISER MENTIONS TO
 REPLACE EXISTING 100A BRKR WITH NEW 150A
 BRKR, HOWEVER IS IS UNCLEAR THE RATING
 OF THE BRKR ENCLOSURE AND METER IS??
 PLEASE PROVIDE INFORMATION ON THIS.
 FBC 106.1.2, ADMIN SECT.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13
 13-415.1.ABC.1.1, .1.2, AND .1.3 FOR
 LIGHTING CONTROLS, SCHEDULING,
 OVER-RIDES DEVICES AND LOCATIONS.
 PLEASE ALSO INDICATE THE TYPE OF OVER
 RIDE DEVICE(S0 ALONG WITH MAX TIME OF
 4HRS PERMITTED FOR TIMER TYPE DEVICES
 AND 30 MINS FOR OCC SENSOR, TYPES.
 PLEASE PROVIDE LPD FOR SPACE.
 13-415.2.AABC.1, 415.2.C.1, 415.2.B.1
  
 4) NOTE: **IMPORTANT**
  
 ONCE ALL REVIEWS ARE DONE AND BEFORE
 PLANS ARE RESUBMITTED, PLEASE COMPLETELY
 REVMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE ONLY.
 ** PLEASE KNOW, THIS WILL HELP IN
 EXPEDITING THE PROJECT AND AVOID ANY
 POSSIBLE DELAYS.
  
 5) NOTE: PLEASE KNOW, ALL THE CURRENT
 ADOPTED CODES AS FOLLOWS SHALL BE
 REFERENCED ON PLANS.
 PLANS STATE LATEST ADOPTED ETC.
 PLEASE PROVIDE THE FOLLOWING AT A MIN,
 2004 FBC, 2002 NFPA-70(NEC), 2002
 NFPA-72, 2003 NFPA-101.
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717