| 2006-07-17 00:00:00 | 1) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | ------------------------------------- |
| | ) NUMBER OF FLOORS |
| | ) SQ. FT. FOOTPRINT |
| | ) SQ. FT. UNDER ROOF (TOTAL) |
| | ) OCCUPANT LOAD |
| | ) FLOOD ZONE |
| | |
| | 2) 11-7.2 SALES AND SERVICE COUNTERS, |
| | TELLER WINDOWS, INFORMATION COUNTERS. |
| | (1) IN DEPARTMENT STORES AND |
| | MISCELLANEOUS RETAIL STORES WHERE |
| | COUNTERS HAVE CASH REGISTERS AND ARE |
| | PROVIDED FOR SALES OR DISTRIBUTION OF |
| | GOODS OR SERVICES TO THE PUBLIC, AT |
| | LEAST ONE OF EACH TYPE SHALL HAVE A |
| | PORTION OF THE COUNTER WHICH IS AT LEAST |
| | 36 INCHES (915 MM) IN LENGTH WITH A |
| | MAXIMUM HEIGHT OF 36 INCHES (915 MM) |
| | ABOVE THE FINISH FLOOR. IT SHALL BE ON |
| | AN ACCESSIBLE ROUTE COMPLYING WITH |
| | SECTION 11-4.3 . THE ACCESSIBLE COUNTERS |
| | MUST BE DISPERSED THROUGHOUT THE |
| | BUILDING OR FACILITY. IN ALTERATIONS |
| | WHERE IT IS TECHNICALLY INFEASIBLE TO |
| | PROVIDE AN ACCESSIBLE COUNTER, AN |
| | AUXILIARY COUNTER MEETING THESE |
| | REQUIREMENTS MAY BE PROVIDED. PROVIDE |
| | THE ELEVATION DETAILS OF THE CHECK OUT |
| | COUNTER. |
| | |
| | 3) SHOW THE EXIT DOOR IN THE REAR OF THE |
| | BUILDING WHERE THE EXIT LIGHT IS. SEE |
| | REFLECTED CEILING PLAN SHEET A-2. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | |
| | |