| Plan Review Notes For Permit 06061640 |
| Permit Number |
06061640 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-04 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | | | | 1.)THE ENGINEER'S CALCULATION FOR THE | | | ENHANCED FASTENING FOR ZONES 2 AND 3 | | | SPECIFY A DESIGN PRESSURE OF -60PSF. | | | THE APPROVED ASSEMBLY YOU HAVE CHOSEN | | | HAS A DESIGN PRESSURE OF -52.5. | | | |
|