| Plan Review Notes For Permit 06061626 |
| Permit Number |
06061626 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-02 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | 1.A NOTICE OF COMMENCEMENT MUST | | | BE FILED WITH THE CLERK OF COURTS BEFORE | | | A PERMIT CAN BE ISSUED, FS713.13. | | | | | | 2.YOU HAVE PROVIDED TWO DIFFERENT SETS | | | OF COMPUTERIZED ENGINEERING FOR DESIGN | | | PRESSURES FOR THIS JOB.BOTH HAVE | | | DESIGN PRESSURES FOR ENCLOSED AND | | | PARTIALLY ENCLOSED BUILDINGS, NOT CLEAR | | | WHICH CONDITION YOU ARE USING.SOME OF | | | THE DESIGN PRESSURES SPECIFIED ARE | | | GREATER THAN -60, BUT YOU HAVE CIRCLED | | | -60PSF ON THE ANCHOR SCHEDULE.IF YOU | | | DO NOT UNDERSTAND THIS CORRECTION OR | | | NEED ASSISTANCE IN DETERMINING HOW TO | | | CORRECT THIS, PLEASE CONTACT ME. |
|