| Plan Review Notes For Permit 06061623 |
| Permit Number |
06061623 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-04-02 07:37:32 | DENIED; | | | 1.REVISED DRAWINGS ARE NOT DRAWN BY THE DESIGN | | | PROFESSIONALS ON RECORD. | | | 2.PAGE A3.09 KITCHENETTE ; CABINET TO BE OPEN UNDER THE | | | SINK FOR KNEE SPACE SEEFBC-2004 BUILDING SECTION | | | 11-4.24.3. | | | 3.SUBMIT SANITARY AND WATER RISER DIAGRAMS. | | | 4.LIST PLUMBING FIXTURES, SHOW MANUFACTURE OF 2 | | | COMPARTMENT SINK AND FLOOR SINK. | | | 5.PAGE P3.01, KEY NOTES; NOTE 1 CALLS FOR HOT WATER, NO | | | WATER HEATER SHOWN ON PLANS AND NO ELECTICAL SHOWN ON | | | PANEL RISER DIAGRAM. | | | NOTE 53" CONDENSATE DRAIN TO RUN DOWN | | | STREAM OF THE BATHROOM GROUP, SEE FBC-2004 SECTION | | | 909.1.NOTE 6, TRAP TO BE 1 1/2" FOR SINK. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|