Plan Review Notes
Plan Review Notes For Permit 06061623
Permit Number 06061623
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-09 10:30:16 
  
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE PROVIDE THE PANEL DESIGNATION AND CIRCUIT
 NUMBERS FOR ALL RECEPTACLES AND LIGHT FIXTURES AFFECTED
 UNDER THIS PERMIT. 106.3.5.1.2 FBC AS AMENDED.
  
 2} THE RECEPTACLE FOR THE REFRIGERATOR IN THE
 KITCHENETTE, SHEET E3.01, MUST BE GFI PER 210.8(B)(3),
 2002 NEC.
  
 3} PLEASE SHOW COMPLIANCE WITH MEANS OF ILLUMINATION
 FOR THE STAIRWELLS PER 1006.2FBC AND 7.9 NFPA-101.
  
 4} PLEASE GIVE THE RATING OF THE DISCONNECT FOR THE
 "NEW A/C UNIT" ON SHEET E3.01, AS WAS DONE FOR THE TWO
 EXISTING.
  
 5} THE LOADS HAVE BEEN REMOVED FROM THE PANEL SCHEDULES
 ON SHEET E3.03. PROVIDE THE CALCULATIONS PER 220 NEC
 AND SHOW CONNECTED LOADS.
  
 5} INDICATE THE LOCATIION AND ADD TO THE PANEL SCHEDULE
 THE ROOFTOP RECEPTACLE REQUIRED BY 210.63, NEC.
 AS APPLICABLE.
  
 PLEASE NOTE THAT HAND DRAWN CHANGES TO THE PLAN ARE NOT
 ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE BY
 THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481, AS
 APPLICABLE.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718