FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-19 00:00:00 | ***PROVISO*** | | | | | | THOUGH REQUESTED FROM FIRST FIRE REVIEW, | | | NO ADDITIONAL INFORMATION FOUND | | | REGARDING STAIRS. ALL STAIRS SHALL | | | COMPLY WITH NFPA 101, 2003 EDITION, | | | SECTION 7.2.2.2.19(A). PLEASE PROVIDE | | | NOTE REGARDING PRESCRIPTIVE STRENGTH | | | REQUIREMENT FOR HANDRAILS AND GUARDS. | | | | | | THIS WRITER UNDERSTANDS PRIOR APPROVAL, | | | HOWEVER UPDATED OR NEW PLANS WILL BE | | | REFERENCED DURING INSPECTION, AND SHOULD | | | REFLECT REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|