Plan Review Notes
Plan Review Notes For Permit 06061612
Permit Number 06061612
Review Stop G
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED ON THE ISOMETRIC DRAWING
 RESUBMITTAL FOR GAS PLAN REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.(NOTE: THE ISOMETRIC
 DRAWING RESUBMITTED INDICATES AN 1-1/2"
 GALVANIZED PIPE GOING FROM THE METER 10'
 UP IN THE AIR IS THIS YOUR INTENT?
 PLEASE REMEMBER THAT GALVANIZED PIPE
 UNDER GROUND IS UNACCEPTABLE PER
 FBC-2004 FUEL GAS SECTION 404.8. ALSO
 PLEASE INDICATE EXISTING GAS SYSTEM ON
 ISOMETRIC DRAWING.)
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).(NOTE: THIS INCLUDES THE
 EXISTING BTU LOAD OF THE POOL HEATER,
 AGAIN PLEASE SEE ATTACHED PERMIT
 INFOMATION INDICATING GAS AT SAID
 ADDRESS.)
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).(NOTE: AGAIN
 THIS INCLUDES EXISTING GAS ON SYSTEM,
 LONGEST LENGTH METHOD USED TO SIZE GAS
 SYSTEM, THAT MEANS ENTIRE SYSTEM.)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  