| 2006-08-07 00:00:00 | ******DENIED 2ND TIME****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED FOR GAS PLAN REVIEW ON THE |
| | ISOMETRIC DRAWING: |
| | |
| | 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| | A GEN/RES PERMIT APPLICATION HAS BEEN |
| | APPLIED FOR AND APPROVED BY ZONING FOR |
| | THE GENERATOR LOCATION. (NOTE: THERE IS |
| | STILL NO GENERATOR PERMIT APPLICATION |
| | APPLIED FOR AT SAID ADDRESS) |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. ( NOTE: THE ISOMETRIC |
| | SUBMITTED IN THE RESUBMITTAL IS |
| | UNACCEPTABLE, IT SHALL INDICATE THE |
| | EXISTING SYSTEM TEE TIE IN, 1ST AND 2ND |
| | STAGE REGULATORS, BOTH ABOVE AND BELOW |
| | GROUND PIPING, VALVES AND DIRT LEGS.THE |
| | ONLY INDICATION OF PIPE IS THE 50' OF |
| | UNDER GROUND PE, ALL PIPES AND |
| | CORRESPONDING LENGTHS SHALL BE INDICATED |
| | ON THE ISOMETRIC DRAWING, NEW ABOVE AND |
| | BELOW GROUND AND THE EXISTING SYSTEM TO |
| | THE BEST OF THE INFORMATION KNOWN.) |
| | 3. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | (NOTE: AGAIN ALL PIPE MATERIAL AND SIZES |
| | SHALL BE INDICATED ON THE ISOMETRIC |
| | DRAWING.) |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).(NOTE: AGAIN THE BTU LOAD OF |
| | THE SYSTEM SHALL BE INDICATED ON THE |
| | ISOMETRIC DRAWING. THIS INCLUDES THE |
| | EXISTING SYSTEM AS WELL AS THE NEW |
| | GENERATOR. PLEASE SEE ATTACHED PERMIT |
| | INFORATION INDICATING EXISTING GAS AT |
| | SAID ADDRESS.) |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (NOTE: THIS |
| | INCLUDES THE EXISTING SYSTEM BECAUSE |
| | SYSTEM IS SIZED BY THE LONGEST LENGTH |
| | METHOD.) |
| | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 (NOTE: |
| | MANUFACTURE CUT SHEETS ON THE 1ST AND |
| | 2ND STAGE REGULATORS.TWO COPIES |
| | REQUIRED) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |