| 2006-08-07 00:00:00 | ******DENIED 2ND TIME****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED ON THE RESUBMITTED ISOMETRIC |
| | FOR GAS PLAN REVIEW: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE.(NOTE: THE RESUBMITTED |
| | ISOMETRIC DRAWING INDICATES AN 1-1/2" |
| | GALVANIZED GAS PIPE GOING 16" UP IN THE |
| | AIR, IS THIS YOUR INTENT. PLEASE SEE THE |
| | ATTACHED EXAMPLES OF ISOMETRICS IN RED |
| | INK FOR REFERENCE FOR RESUBMITTAL.) |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | (NOTE: GALVANIZED PIPE UNDER GROUND |
| | UNACCEPTABLE PER FBC-2004 FUEL GAS |
| | SECTION 404.8. PLEASE INDICATE IF GAS |
| | PIPE IS ABOVE OR BELOW GROUND.) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |