| Plan Review Notes For Permit 06061599 |
| Permit Number |
06061599 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-12 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PLAN SHOWS BOTH OVERHEAD AND | | | UNDERGROUND SERVICE. INDICATE WHICH IT | | | IS OR WILL BE, ALSO WHETHER EXISTING OR | | | NEW. | | | | | | 2} THE LOAD CALCULATIONS SHOW 50% ON | | | CERTAIN LOADS WHICH CODE SECTION WOULD | | | REGULATE THIS PRACTICE, ONLY RECEPTACLE | | | OUTLETS HAVE THIS TYPE OF DEDUCTION. | | | | | | 3) ON BUILDING LAYOUT SHOW WHERE THE | | | SERVICE IS LOCATED, SHOW ALL MAINS OFF | | | THIS SERVICE. | | | | | | JAKE LEAHY644-7291 |
|