Text |
| 2006-08-25 00:00:00 | *** DENIED *** |
| | 1) PLEASE SEE ELECTRICAL REVIEW NOTES |
| | AND CORRECT. |
| | 2) PLEASE SEE THE FOLLOWING NOTES |
| | REGARDING GENERATOR LOCATION. |
| | 3) PER 2004 FBC, FUEL GAS - POWERED |
| | EQUIPMENT - PERMANENTLY INSTALLED |
| | EQUIPMENT POWERED BY INTERNAL COMBUSTION |
| | ENGINES SHALL BE INSTALLED IN ACCORDANCE |
| | WITH MANUFACTURE'S INSTALLATION |
| | INSTRUCTIONS AND NFPA 37. |
| | |
| | NFPA 37 INSTALLATION & USE OF STATIONARY |
| | COMBUSTION ENGINES & GAS TURBINES: |
| | 4.1.4ENGINES (GENERATORS) LOCATED |
| | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM |
| | OPENINGS IN WALLS & AT LEAST 5 FT FROM |
| | STRUCTURES HAVING COMBUSTIBLE WALLS.A |
| | MINIMUM CLEARANCE IS NOT REQUIRED WHEN |
| | (1) THE ADJACENT WALL HAS A MINIMUM FIRE |
| | RESISTANCE RATING OF 1 HOUR OR (2) THE |
| | WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NON-COMBUSTIBLE MATERIALS, AND IT HAS |
| | BEEN DEMONSTRATED THAT A FIRE WITHIN THE |
| | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS OUTSIDE THE ENCLOSURE. |
| | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS |
| | SHOULD NOT TERMINATE UNDER STRUCTURES OR |
| | WHERE THE EXHAUST MIGHT BE DRAWN INTO |
| | THE VENTILATION INTAKES. |
| | |
| | 2004 FMC 804.3.5 #3, WHERE THE |
| | TERMINATION IS LOCATED BELOW AN ADJACENT |
| | ROOF STRUCTURE, THE TERMINATION POINT |
| | SHALL BE LOCATED AT LEAST 3 FT FROM THE |
| | ROOF STRUCTURE. |
| | |
| | PLEASE NOTE, WHILE ZONING ALLOWS |
| | MECHANICAL EQUIPMENT TO ENCROACH 4 FT |
| | INTO THE REQUIRED SETBACK, GENERATORS |
| | SHALL MAINTAIN THE REQUIRED ABOVE |
| | MENTIONED CLEARANCES TO THE ADJACENT |
| | PROPERTY STRUCTURES, I.E. FENCE, |
| | BUILDING, WINDOWS, DOORS, OR OPENINGS. |
| | |
| | FOLLOW MANUFACTURE'S RECOMMENDED |
| | CLEARANCES AROUND EQUIPMENT FOR |
| | SERVICING,AND PROVIDE MANUFACTURE'S |
| | INSTALLATION INSTRUCTIONS AT THE JOBSITE |
| | FOR THE FIELD INSPECTOR. |