2007-02-02 14:33:53MECHANICAL REVISION
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS ON FILE ARE CALLING FOR
 UNIT #1 31,100 SENSIBLE BTU'S, AND UNIT #2 32,200
 SENSIBLE BTU'S, REVISED PLANS ARE SHOWING 27,000
 SENSIBLE BTU'S. THE PLANS MAY NOT CALL FOR LESS THAN
 THE COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1.1. YOU NEED TO REVISE THE COOLING LOAD
 CALCULATIONS OR THE EQUIPMENT LISTING ON THE PLANS.
  
 2) REVISED PLANS ARE CALLING FOR 1" THICK INSELATION
 DUCTS (R-4). ALL A/C DUCT WORK NOT IN CONDITIONED
 SPACES MUST BE R-6 (1.5" THICK INSULATION, PER 2004 FBC
 13-610.1.B.1.
  