Plan Review Notes
Plan Review Notes For Permit 06061582
Permit Number 06061582
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-13 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 2/0 FEEDERS FROM THE METER TO THE
 GUTTER ARE NOTLARGE ENOUGH FOR THE LOAD
 SERVED. THE FEED WOULD BE OK IF
 PARALLELED.
  
 2} THE GENERATOR AND TRANSFER SWITCH
 MUST BE PERMITTED SEPARATELY. THE
 CONFIGURATION IS TENETAVELY OK.
  
 3} THE NEUTRAL IS NOT ISOLATED FROM THE
 GROUND UNTILL THE FIRST MEANS OF
 DISCONNECT TO PREVENT PARALLELING GROUND
 AND RETURN PATHS, THEREFORE THE GROUND
 WIRE SHOULD NOT BE RUN WITH THE SERVICE
 CONDUCTORS FROM THE METER. 250.4(A)(5).
  
 4} PANEL "A" DOES NOT SHOW THE DEMAND
 LOADS, CANNOT VERIFY OCP AN DWIRE
 SIZE.310.16, 240.4.
  
 5} AHU #3 INDICATES #14 WIRE ON A 15 AMP
 BREAKER. PLEASE CHECK THE DEMAND AND
 SHOW SAME. ALSO CHECK A/C #3.
  
 6} THE RISER INDICATES THE SERVICE
 ATTACHED WITH A GUTTER. THE PLANS SHOW
 THE ATS AND METER OUTSIDE, AND THE
 PANELS INSIDE, PLEASE CLARIFY.
  
 7} THE WHIRLPOOL IN THE MASTER BATH IS
 NOT IN THE CALCS.
  
 8} INDICATE THE ROOM DESIGNATIONS ON THE
 ELECTRICAL PLAN. SHEET E-1 AND A-1 ARE
 NOT THE SAME FLOOR PLAN.
  
 THERE WILL BE NO FURTHER ELECTRICAL
 REVIEW UNTILL ITEM #8 IS CORRECTED.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  
  