| Plan Review Notes For Permit 06061549 |
| Permit Number |
06061549 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-08-22 21:07:47 | | | | *** DENIED *** | | | | | | | | | 1) NOTE: PLEASE SEE KITCHEN SMALL APPLIANCE RECEPTACLE | | | IS BEING SHOWN ON WITH THE BATHS RECEPTACLE. THIS IS | | | ALSO BEING SHOWN IN HALLWAY? | | | PLEASE SEE MISSING REQUIRED TWO FOR KITCHEN. PLEASE SEE | | | COUNTER SPACE AREA WIHT NO GFI.TS, KITCHEN LIGHTS ETC | | | WHICH IS NOT PERMITTED. | | | PLEASE SEE THE LOAD CALCULATIONS ALSO INCLUDE THIS IN | | | THE LOADS OF THE SMALL APPLIANCES. | | | RECEPTACLE REQUIRED TO BE FIGURED PER 210.52B1, 220.16, | | | 210.11C2 | | | | | | 2) NOTE: PLEASE SEE PREVIOUS LETTERS FROM ORIGINAL | | | ENGINEER WERE REDLINED, HOWEVER PLEASE SEE AS PLANS ARE | | | COMING BACK, PLEASE SEE THE LETTER OF RELEASE IS MADE | | | OUT TO *PALM BEACH COUNTY* BUILDING DEPARTMENT. SCOPE | | | OF WORK IS NOT LOCATED IN PALM BEACH COUNTY. | | | THIS SHOULD BE: | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | | | | ** PANEL BEING SHOWN AS *EXISTING* ? WERE THESE NOT ALL | | | CHANGED OUT? | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|