2007-10-29 07:59:22 
  
  
 PROVISO
  
 THE RISER DIAGRAM HAS BEEN REDLINED TO CORRECT
 GROUNDING AND LINE AND LOAD IN THE SAME CONDUIT ISSUES.
 SEE 230.7, 250.66, 250.122, AND 225.32, 2005 NEC.
 CORRECT THE RISER PRIOR TO CALLING THE SERVICE
 INSPECTION, AND SUBMIT FOR REVIEW. SEE THAT THE
 DESIGNER OF RECORD GETS THE REDLINED COPY SO HE CAN
 READ THOSE ARTICLES CONCERNED AND MAKE THE CORRECTIONS
 NECESSARY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  