Plan Review Notes
Plan Review Notes For Permit 06061539
Permit Number 06061539
Review Stop E
Sequence Number 5
Notes
Date Text
2007-09-04 10:06:58 
  
  
  
 DENIED
 THESE COMMENTS WERE APROVISO ON THE PREVIOUS REVIEW
 AND HAVE NOT BEEN CORRECTED AS REQUIRED.
  
 THE SERVICE RISER HAS CHANGED SINCE THE PREVIOUS
 REVIEW. MAKE THE FOLLOWING CHANGES FOR CODE COMPLIANCE
 AND RESUBMIT FOR REVIEW PRIOR TO CALLING AN INSPECTION
 ON THE SERVICE.
  
 1} ON SHEET E-1 THERE IS A "MAIN DISCONNECT" SHOWN AT
 THE SERVICE, THE RISER THERE IS SHOWN SEPERATE
 DISCONNECTS FOR "A" "B" AND "C". CORRELATE SAME.
 DISCONNECT "C" IS ON THE GARAGE, NOT AT THE HOUSE.
  
 2} THE GROUNDING ELECTRODE NEEDS TO BE AT THE METER OR
 GUTTER, NOT AT THE PANELS. SEE REDLINED PLAN.
  
 3}THE GROUNDING CONDUCTOR MUST BE A MINIMUM #2 CU PER
 250.66. INDICATE SAME ON PLANS.
  
 4} LOCATE THE DISCONNECTS AHEAD OF THE PANELS ON THE
 RISER, NOT IN PARALLEL WITH THEM. SEE REDLINE. INDICATE
 AMPERAGE ON THE DISCONNECTS.
  
 THE REVIEWED PLAN MUST BE ON THE JOB
 SITE AT TIME OF INSPECTION. ALLOW AT
 LEAST ONE WEEK (PER TRADE) FOR PLAN
 REVIEW.
  
 THESE ARE COMMENTS FROM THE REVIEW DONE ON 9/4/07
  
 1} THIS WAS SUBMITTED AS A RESTAMP AS IN FACT A
 REVISION. TWO SETS OF PLANS ARE REQUIRED FOR A REVISION
 PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718