| Plan Review Notes For Permit 06061539 |
| Permit Number |
06061539 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-05-04 15:43:36 | | | | | | | PROVISO | | | THE SERVICE RISER HAS CHANGED SINCE THE PREVIOUS | | | REVIEW. MAKE THE FOLLOWING CHANGES FOR CODE COMPLIANCE | | | AND RESUBMIT FOR REVIEW PRIOR TO CALLING AN INSPECTION | | | ON THE SERVICE. | | | | | | 1} ON SHEET E-1 THERE IS A "MAIN DISCONNECT" SHOWN AT | | | THE SERVICE, THE RISER THERE IS SHOWN SEPERATE | | | DISCONNECTS FOR "A" "B" AND "C". CORRELATE SAME. | | | DISCONNECT "C" IS ON THE GARAGE, NOT AT THE HOUSE. | | | | | | 2} THE GROUNDING ELECTRODE NEEDS TO BE AT THE METER OR | | | GUTTER, NOT AT THE PANELS. SEE REDLINED PLAN. | | | | | | 3}THE GROUNDING CONDUCTOR MUST BE A MINIMUM #2 CU PER | | | 250.66. INDICATE SAME ON PLANS. | | | | | | 4} LOCATE THE DISCONNECTS AHEAD OF THE PANELS ON THE | | | RISER, NOT IN PARALLEL WITH THEM. SEE REDLINE. INDICATE | | | AMPERAGE ON THE DISCONNECTS. | | | | | | THE REVIEWED PLAN MUST BE ON THE JOB | | | SITE AT TIME OF INSPECTION. ALLOW AT | | | LEAST ONE WEEK (PER TRADE) FOR PLAN | | | REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|