| 2007-10-29 11:13:12 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | MECHANICAL REVISION | | | *** DENIED *** | | | 1) PROVIDE FOR RETURN AIR TO THE MEDIA ROOM, SEE FBC/R | | | M1602.4. | | | | | | 2) RETURN AIR GRILL IN THE RECREATION ROOM NEEDS TO BE | | | SIZED (SEE YELLOW HIGH LIGHT ON MECH. PLAN). | | | | | | 3) SUPPLY AIR DUCT FROM AIR HANDLER TO MIXING BOX ABOVE | | | MASTER BATHROOM NEEDS TO BE SIZED (SEE YELLOW HIGH | | | LIGHT ON MECH. PLAN). | | | | | | 4) RETURN AIR DUCT FROM AIR HANDLER TO BEDROOM #3 NEEDS | | | TO BE SIZED (SEE YELLOW HIGH LIGHT ON MECH. PLAN). | | | | | | 5) RETURN AIR DUCT FROM AIR HANDLER TO MASTER BEDROOM | | | NEEDS TO BE SIZED (SEE YELLOW HIGH LIGHT ON MECH. | | | PLAN). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|