2007-10-29 11:13:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) PROVIDE FOR RETURN AIR TO THE MEDIA ROOM, SEE FBC/R
 M1602.4.
  
 2) RETURN AIR GRILL IN THE RECREATION ROOM NEEDS TO BE
 SIZED (SEE YELLOW HIGH LIGHT ON MECH. PLAN).
  
 3) SUPPLY AIR DUCT FROM AIR HANDLER TO MIXING BOX ABOVE
 MASTER BATHROOM NEEDS TO BE SIZED (SEE YELLOW HIGH
 LIGHT ON MECH. PLAN).
  
 4) RETURN AIR DUCT FROM AIR HANDLER TO BEDROOM #3 NEEDS
 TO BE SIZED (SEE YELLOW HIGH LIGHT ON MECH. PLAN).
  
 5) RETURN AIR DUCT FROM AIR HANDLER TO MASTER BEDROOM
 NEEDS TO BE SIZED (SEE YELLOW HIGH LIGHT ON MECH.
 PLAN).
  