Plan Review Notes
Plan Review Notes For Permit 06061539
Permit Number 06061539
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-11 09:31:03NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE DISCONNECTING MEANS FOR PANEL"C" IN THE GARAGE
 MUST BE LOCATED ON THE GARAGE, NOT ON THE HOUSE. SEE
 225.32 FOR CLARITY.
  
 2} IT IS ASSUMED THAT THE GARAGE FEED ORIGINATES FROM
 THE 200 AMP MAIN DISCONNECT, WHICH IS APPARANTLY DOUBLE
 LUGGED. BUT CIRCUIT #37 IN PANEL "B" LISTS' PNL "C"
 GARAGE" FED WITH A # 12 CONDUCTOR FROM A 20 AMP
 BREAKER. PLEASE CORRELATE.
  
 3} A/C #1 IS IS BEING FED FROM PANEL "B" IN THE
 SCHEDULE, AND PANEL "A" ON THE RISER DIAGRAM.
  
 4} THE LOAD CALCULATIONS LISTS 3-10,000 WATT HEAT
 STRIPS. THERE ARE ONLY 2 AHU'S IN THE PANEL SCEDULES @
 10K, AND ONLY TWO LISTED ON THE MECHANICAL SHEET,
 M-1.PLEASE CORRELATE, CORRECT CALCULATION.
  
 5} THERE ARE 5 SMALL APPLIANCE CIRCUITS LISTED ON
 SCHEDULE"A", AND 1 IN SCHEDULE "C", BUT ONLY 4 IN THE
 CALCULATIONS .PLEASE NOTE PER 210.52(B), THERE IS NO
 REQUIREMENT FOR A SMALL APPLIANCE CIRCUIT IN PANEL "C",
 UNLESS THE GARAGE HAD A SEPARATE KITCHEN.
  
 6} SHEET "E-1" SHOWS A 100 GALLON GAS WATER HEATER. THE
 LOAD CALCULATIONS LIST AN 80 GALLON WATER HEATER @ 5500
 WATTS. PANEL "A" CIRCUIT 30 LISTS A WATER HEATER FED
 FROM A 50 AMP BREAKER ON #12 WIRE, WHICH VIOLATES
 310.16, 240.4(D) AND 422.11(E)(3). THE HEATER IS ALSO
 LISTED AS ELECTRIC IN THE EMNERGY CALCULATIONS, SHEET
 SP.
  
 7} THE DRYER IN SCHEDULE "A" IS FED WITH #12 WIRE ON A
 50 AMP BREAKER THE DRYER IS RATED AT 5000 WATTS (PER
 220.18) IN THE CALCULATION. 5000/240=20.8 AMPS, 25AMP
 BREAKER PER 240.4.
  
 8} THE COOKTOP IN THE CALCULATION IS SHOWN AT 5000
 WATTS ON A 20 AMP BREAKER, AND ON A 50 AMP BREAKER ON
 #12 WIRE IN SCHEDULE "A". SEE 310.16.
  
 9} OVENS 1&2 HAVE #12 WIRE ON A 50 AMP BREAKER,
 310.16.
  
 10} THE AIR HANDLERS IN SCHEDULE "B" HAVE #8 CONDUCTORS
 ON A 60 AMP BREAKER. 310.16.
 10000/240=41.66X125%(424.3(B) NEC)=52 AMPS. #6
 CONDUCTORS, 310.16.
  
 11} THE CALCULATION INDICATES A "MISC" LOAD OF 6000
 WATTS ON A 2 POLE 50 AMP BREAKER, PLEASE LIST THE
 SPECIFIC LOAD PER 220 SECTION I OR SECTION III.
  
 12} THE DISCONNECTS FOR PANELS "A" & "B" SHOWN ON SHEET
 E-1, ARE NOT LOCATED ON THE RISER.
  
 THE LOAD AS IT IS CALCULATED ON THIS PLAN, EXCEEDS THE
 200 AMP SERVICE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  