| 2007-01-03 17:00:42 | DENIED 2ND TIME |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE PER THE |
| | PREVIOUS PLUMBING PLAN REVIEW: |
| | |
| | 1. SHEET P-1 ICE MAKER, DRAIN REQUIRED PER FBC-2004 |
| | PLUMBING, SECTION 802.1.3, AND THE SUBMITTED |
| | MANUFACTURER SHEETS. THE RESUBMITTED DRAWINGS INDICATE |
| | THE ICE MAKER IN THE CABANA BEING DELETED, IS THIS THE |
| | INTENT OR IS A DRAIN NEED TO BE PROVIDED FOR THAT ICE |
| | MAKER AS WELL. PLEASE CLARIFY AND PLEASE ADD DRAINS |
| | WHERE NEEDED ON THE RESUBMITTAL. |
| | |
| | 2. SHEET P-1 SANITARY RISER DIAGRAM, THE FIRST FLOOR |
| | LAV IN THE MEDIA ROOM BATH IS STILL WRONG. THE SECOND |
| | FLOOR BATHROOM RISERS CAN'T DISCHARGE INTO THAT LAVS |
| | VENT PER FBC-2004 PLUMBING, SEC. 909.1 AND 909.1.1. |
| | PLEASE CORREC ON THE RESUBMITTAL. |
| | |
| | 3.(OK) |
| | |
| | 4. (OK) |
| | |
| | THE FOLLOWING ARE NEW COMMENTS THAT NEED TO BE |
| | ADDRESSED DUE TO THE RESUBMITTAL OF NEW P-1 SHEET: |
| | |
| | 5. PLEASE DELETE THE S.V. ON THE KITCHEN SINK ON THE |
| | RESUBMITTAL DUE TO THE FACT THAT THE SINK IS INDICATING |
| | A 3" V.T.R. |
| | |
| | 6. SHEET P-1, PLUMBING NOTES: #19. PLEASE DELETE SFBC |
| | SECT. 4613 THAT CODE IS NO LONGER IN USE AS OF 2001. |
| | PLEASE ADD THE FOLLOWING, FBC-2004 TABLE 604.3 WATER |
| | DISTRIBUTION DESIGN CRITERIA REQUIRED CAPACITY AT |
| | FIXTURE SUPPLY OUTLETS. |
| | |
| | ******IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |