Plan Review Notes
Plan Review Notes For Permit 06061539
Permit Number 06061539
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-19 16:48:27NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} PER THE RISER DIAGRAM AND FLOOR PLAN, THE PANELS "A"
 & B" IN THE RESIDENCE, THE DISCONNECTING MEANS DO NOT
 COMPLY WITH 230.70(A)(1) READILY ACCESSIBLE LOCATION.
 THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A
 READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS.DISCONNECTS MUST BE
 OUTSIDE AT THE SERVICE LOCATION.
  
 3} THERE IS NO FEEDER LISTED IN THE
 SCHEDULE, FROM PANEL "A" TO THE GARAGE
 PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]