| Plan Review Notes For Permit 06061539 |
| Permit Number |
06061539 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-19 16:48:27 | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 2} PER THE RISER DIAGRAM AND FLOOR PLAN, THE PANELS "A" | | | & B" IN THE RESIDENCE, THE DISCONNECTING MEANS DO NOT | | | COMPLY WITH 230.70(A)(1) READILY ACCESSIBLE LOCATION. | | | THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A | | | READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A | | | BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF | | | ENTRANCE OF THE SERVICE CONDUCTORS.DISCONNECTS MUST BE | | | OUTSIDE AT THE SERVICE LOCATION. | | | | | | 3} THERE IS NO FEEDER LISTED IN THE | | | SCHEDULE, FROM PANEL "A" TO THE GARAGE | | | PANEL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|