| 2007-02-02 12:58:36 | DENIED BY BUILDING |
| | |
| | 1) THE ROOF SHEATHING FASTENING NOTE THAT HAS BEEN |
| | GLUED TO SHEET S3 IS NOT ACCEPTABLE. THIS INFORMATIONIS |
| | REQUIRED TO BE ON THE SIGNED AND SEALED DRAWINGS. |
| | |
| | 2) THE 2' X 2' MASONRY COLUMNS AT THE EXTERIOR ON THE |
| | BALCONY FRAMING PLAN ON S/3 ARE MIOSLABELED AS C3. SEE |
| | RED MARKINGS ON THEPLAN. |
| | |
| | 3)SECTIONS 7/S5 SHOWN ON S3 THROUGH THE NEW BALCONY |
| | IS IN THE WRONG LOCATION. SEE RED MARK ON PLANS. |
| | |
| | 4) SECTIONS 7/S5 AND 9/S5 BOTH SHOWN AT THE EAST |
| | CABANA/OUTSIDE LIVING AREA ON S3 DO NOT CONCUR. ONE HAS |
| | A PARAPET HEIGHT OF 11' AND THE OTHER HAS 15'-8". SEE |
| | MARKS ON THE PLAN. |
| | |
| | 5) THE ELEVATIONS FOR THE CABANA/OUTDOOR LIVING AREA ON |
| | A3 DO NOT CORRESPOND WITH THE ONES IN THE SECTIONS ON |
| | S5. PLEASE CORRECT. |
| | |
| | 6) PROVIDE BUCK DETAILS FOR THE OVERHEAD GARAGE DOORS. |
| | |
| | 7) PROVIDE WALL SECTIONS OF THENON-LOAD INTERIOR |
| | BEARING PARTIONS. SPECIFY THE FRAMING MATERIAL, |
| | SPACING, FINISHES, ETC. |
| | |
| | 8) PROVIDE EXTERIOR WALL SECTIONS, SPECIFYING THE |
| | FURRING, INSULATION, INTERIOR AND EXTERIOR COVERINGS, |
| | ETC. |
| | |
| | 9) SPECIFY THE FINISH/COVERING OF THE CABANA/OUTDOOR |
| | LIVING AREA CEILING. |
| | |
| | 10)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 11)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. BOTH COPIES OF PRODUCT |
| | APPROVALS TO BE SIGNED. |
| | |
| | 12) SUBMIT PRODUCT APPROVALS FOR LARGE MISSILE IMPACT |
| | RATED GLASS WALL STOREFRONTS AND STOREFRONT DOORS. |
| | |
| | 13)SUBMIT CURRENT PRODUCT APPROVALS FOR THE ALUMINUM |
| | RAILING SYSTEM. THE ONE THAT WAS SUBMITTED IS EXPIRED. |
| | |
| | 14) SUBMIT CURRENT PRODUCT APPROVALS FOR THE PGT LARGE |
| | MISSILE IMPACT RATED OUTSWING ALUMINUM FRENCH DOOR. THE |
| | ONE THAT WAS SUBMITTED IS EXPIRED. |
| | |
| | 15)THE DRAWINGS ON SHEETS 1-13 OF THE PRODUCT |
| | APPROVAL FOR THE PGT LARGE MISSILE IMPACT RATED |
| | CASEMENT WINDOWS ARE MISSING THE TOP OF THE PAGES. |
| | PLEASE REPLACE THESE WITH COMPLETE PAGES. |
| | |
| | 16) ON THE PRODUCT APPROVAL FOR THE ROOF COVERING |
| | SPECIFY THE SYSTEM THAT WILL BE INSTALLED. UNDER THE |
| | SYSTEM CIRCLE THE FASTENING OPTION AND DESIGN PRESSURE. |
| | IF THE DESIGN PRESSURE IS LESS THAN REQUIRED IN THE |
| | PERIMETER AND CORNER ZONES AND THE LIMITATIONS ALLOW |
| | ENHANCED FASTENING PROVIDE RAS 117 CALCULATIONS. IF |
| | LIMITATION #7 REQUIRES THESE CALCULATIONS FROM AN |
| | ARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT, |
| | SUBMIT THE SIGNED AND SEALED CALCULATIONS. |
| | |
| | 17) SUBMIT THE LISTING INFORMATION (UL OR OTHER |
| | APPROVED AGENCY) AND MANUFACTURER'S SPECIFICATIONS FOR |
| | THE PREFAB VENTLESS INTERIOR FIREPLACES LOCATED ON THE |
| | 1ST AND 2ND FLOORS OF THE RESIDENCE. |
| | |
| | 18) SUBMIT THE LISTING INFORMATION FOR THE OUTDOOR GAS |
| | FIREPLACE. |
| | |
| | 19) SUBMIT THE LISTING INFORMATION FOR THE BUILT-IN |
| | BBQ. PROVIDE DOCUMENTATION THAT ALLOWS IT TO BE |
| | INSTALLED ON A COVERED PORCH. |
| | |
| | 20) SUBMIT THE LISTING INFORMATION FOR THE WALL HOOD. |
| | PROVIDE DOCUMENTATION THAT ALLOWS IT TO BE INSTALLED ON |
| | A COVERED PORCH. |
| | |
| | 21) SUBMIT SIGNED AND SEALED TRUSS DRAWING AND LAYOUT, |
| | WHICH HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER |
| | OF RECORD FOR THE STRUCTURE PRIOR TO INSTALLATION. SEE |
| | 2004 FBC RESIDENTIAL R 802.1.6.1. |
| | |
| | 22)PLEASE REMOVE THE EXPIRED PRODUCT APPROVALS AND |
| | ONES THAT ARE NOT BEING USED FROM THE SUBMITTAL |
| | PACKAGE. |
| | |
| | 23)PLEASE REMOVE THE OLD SHEETS FROM THE PLANS AND |
| | INSERT THE NEW REVISED SHEETS INTO THE PLANS, SO THAT |
| | TWO COMPLETE SETS OF PLANS ARE CREATED. THE SHEETS WITH |
| | THE IMPACT FEE STAMP ON THEM SHOULD BE LEFT IN THE |
| | PLANS. ONE SET OF THE OLD SHEETS CAN BE RESUBMITTED |
| | ALONG WITH THE TWO NEW SETS OF PLANS FOR REFERENCE |
| | PURPOSES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |