Plan Review Notes
Plan Review Notes For Permit 06061539
Permit Number 06061539
Review Stop P
Sequence Number 1
Notes
Date Text
2006-07-17 00:00:00DENIED;
 1.ICE MACHINES IN BAR AND CABANA AREA;
 HOW WILL THEY DRAIN? SENT IN SPEC. SHEET
 FOR ICE MACHINES.
 2.THE SECOND FLOOR BATHROOM RISERS CAN
 NOT DICHARGE INTO THE VENT OF THE
 KITCHEN AND THE LAVATORY ON THE FIRST.
 3.THE VEGETABLE SINK IS NOT SHOWN ON
 RISER DIAGRAM.
 4.THE BRANCH DRAIN FOR THE AUTOMATIC
 CLOTHES WASHER IS 3" SEE FBC-2004
 PLUMBING SECTION 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695