| Plan Review Notes For Permit 06061539 |
| Permit Number |
06061539 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-17 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS ARE CALLING FOR | | | TWO 13 SEER A/C SYSTEMS, AND THE MECH. | | | PLANS ARE CALLING FOR TWO 12.25 SEER A/C | | | SYSTEMS, THE TWO MUST COINCIDE PLEASE | | | CORRECT. | | | | | | 2) MANUAL J CAL'S.SYSTEM 2 ARE CALLING | | | FOR 29,301 SENSIBLE BTU'S, MECH. PLANS | | | SYSTEM 2 ARE CALLING FOR 43,800 SENSIBLE | | | BTU'S, THE MECH. PLANS CAN ONLY CALL FOR | | | 20% MORE THAN THE MANUAL J CAL'S., PER | | | 2004 FBC 13-607.1.ABC.1.1 . PLEASE | | | CORRECT. | | | | | | 3) RETURN AIR DUCT TO MASTER SUITE NEED | | | TO BE 14" PER 2004 FBC/R M1602.4 . | | | | | | 4) PLEASE SUBMIT DETAILED MANUFACTURE'S | | | SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS FOR NEW GAS FIREPLACES. | | | | | | 5) PLEASE PROVIDE COMBUSTION AIR FOR GAS | | | CLOTHES DRYER, AND GAS WATER HEATER, PER | | | 2005 FBC/R M1701.1 . | | | | | | 6) PLEASE SHOW LOCATION OF CLOTHES DRYER | | | VENT ,AND BATYROON EXHAUST FANS ON MECH. | | | PLANS. | | | | | | 7) OPEN GAS GRILL IN COVERED OUTDOOR | | | LIVING SPACE WILL NEED AN APPROVED | | | EXHAUST HOOD, PER 2004 FBC/M 505.3 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|