Plan Review Notes
Plan Review Notes For Permit 06061539
Permit Number 06061539
Review Stop M
Sequence Number 1
Notes
Date Text
2006-07-17 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 TWO 13 SEER A/C SYSTEMS, AND THE MECH.
 PLANS ARE CALLING FOR TWO 12.25 SEER A/C
 SYSTEMS, THE TWO MUST COINCIDE PLEASE
 CORRECT.
  
 2) MANUAL J CAL'S.SYSTEM 2 ARE CALLING
 FOR 29,301 SENSIBLE BTU'S, MECH. PLANS
 SYSTEM 2 ARE CALLING FOR 43,800 SENSIBLE
 BTU'S, THE MECH. PLANS CAN ONLY CALL FOR
 20% MORE THAN THE MANUAL J CAL'S., PER
 2004 FBC 13-607.1.ABC.1.1 . PLEASE
 CORRECT.
  
 3) RETURN AIR DUCT TO MASTER SUITE NEED
 TO BE 14" PER 2004 FBC/R M1602.4 .
  
 4) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR NEW GAS FIREPLACES.
  
 5) PLEASE PROVIDE COMBUSTION AIR FOR GAS
 CLOTHES DRYER, AND GAS WATER HEATER, PER
 2005 FBC/R M1701.1 .
  
 6) PLEASE SHOW LOCATION OF CLOTHES DRYER
 VENT ,AND BATYROON EXHAUST FANS ON MECH.
 PLANS.
  
 7) OPEN GAS GRILL IN COVERED OUTDOOR
 LIVING SPACE WILL NEED AN APPROVED
 EXHAUST HOOD, PER 2004 FBC/M 505.3 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.