Plan Review Notes
Plan Review Notes For Permit 06061539
Permit Number 06061539
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-12 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} REGARDING THE GARAGE,225.31
 DISCONNECTING MEANS.
 MEANS SHALL BE PROVIDED FOR
 DISCONNECTING ALL UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE BUILDING
 OR STRUCTURE.THE DISCONNECTING MEANS
 SHALL BE AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE
 OF THE CONDUCTORS.
  
 3} REGARDING THE PANEL LOCATION IN THE
 RESIDENCE, THEY TOO WOULD REQUIRE A
 DISCONNECT OUTSIDE OR IMMEDIATELY INSIDE
 AT THE POINT OF ENTRANCE, SEE 230.6 FOR CLARIFICATION
 ON THIS. ALSO IF THE
 DISCONNECT IS OUTSIDE AND THERE IS A
 GENERATOR ADDED LATER ALL THAT RELATED
 EQUIPMENT COULD BE GROUPED AND THERE
 FORE COMPLIANT.
  
 4} PANEL "C" IS SHOWN IN THE GARAGE. THE
 RISER INDICATES ONLY A "FUTURE POOL"
 PANEL. THE GARAGE CIRCUITS ARE NOT ON
 ANY SCHEDULE. PLEASE CORRECT THIS , ALSO
 CORRECTLY DESIGNATE THE PANEL IN
 QUESTION ON THE PLAN AND ON THE RISER.
  
 5} THERE IS NO FEEDER LISTED IN THE
 SCHEDULE, FROM PANEL "A" TO THE GARAGE
 PANEL.
  
 5} THE REQUIRED BATH CIRCUITS ARE NOT ON
 THE PANEL SCXHEDULE. PLEASE ADD SAME. 210.11(C)(3).
  
 6} THE BEDROOM AFCI CIRCUITS REQUIRED
 PER 210.12, DO NOT APPEAR ON THE PANEL
 SCHEDULES.
  
 7} A SMOKE DETECTORS MUST BE INSTALLED
 TO COMPLY WITH R313.1 3 RESIDENTIAL
 FLORIDA BUILDING CODE, AT THE STAIR ON
 THE FIRST FLOOR.
  
 8} RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A) (1) AND 210.52 (A)(2), SEE
 REVIEWED PLAN FOR LOCATIONS THAT DO NOT
 COMPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718