| 2006-07-12 00:00:00 | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 2} REGARDING THE GARAGE,225.31 |
| | DISCONNECTING MEANS. |
| | MEANS SHALL BE PROVIDED FOR |
| | DISCONNECTING ALL UNGROUNDED CONDUCTORS |
| | THAT SUPPLY OR PASS THROUGH THE BUILDING |
| | OR STRUCTURE.THE DISCONNECTING MEANS |
| | SHALL BE AT A READILY ACCESSIBLE |
| | LOCATION NEAREST THE POINT OF ENTRANCE |
| | OF THE CONDUCTORS. |
| | |
| | 3} REGARDING THE PANEL LOCATION IN THE |
| | RESIDENCE, THEY TOO WOULD REQUIRE A |
| | DISCONNECT OUTSIDE OR IMMEDIATELY INSIDE |
| | AT THE POINT OF ENTRANCE, SEE 230.6 FOR CLARIFICATION |
| | ON THIS. ALSO IF THE |
| | DISCONNECT IS OUTSIDE AND THERE IS A |
| | GENERATOR ADDED LATER ALL THAT RELATED |
| | EQUIPMENT COULD BE GROUPED AND THERE |
| | FORE COMPLIANT. |
| | |
| | 4} PANEL "C" IS SHOWN IN THE GARAGE. THE |
| | RISER INDICATES ONLY A "FUTURE POOL" |
| | PANEL. THE GARAGE CIRCUITS ARE NOT ON |
| | ANY SCHEDULE. PLEASE CORRECT THIS , ALSO |
| | CORRECTLY DESIGNATE THE PANEL IN |
| | QUESTION ON THE PLAN AND ON THE RISER. |
| | |
| | 5} THERE IS NO FEEDER LISTED IN THE |
| | SCHEDULE, FROM PANEL "A" TO THE GARAGE |
| | PANEL. |
| | |
| | 5} THE REQUIRED BATH CIRCUITS ARE NOT ON |
| | THE PANEL SCXHEDULE. PLEASE ADD SAME. 210.11(C)(3). |
| | |
| | 6} THE BEDROOM AFCI CIRCUITS REQUIRED |
| | PER 210.12, DO NOT APPEAR ON THE PANEL |
| | SCHEDULES. |
| | |
| | 7} A SMOKE DETECTORS MUST BE INSTALLED |
| | TO COMPLY WITH R313.1 3 RESIDENTIAL |
| | FLORIDA BUILDING CODE, AT THE STAIR ON |
| | THE FIRST FLOOR. |
| | |
| | 8} RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A) (1) AND 210.52 (A)(2), SEE |
| | REVIEWED PLAN FOR LOCATIONS THAT DO NOT |
| | COMPLY. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | WILLIAM R. TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561) 805-6718 |