Notes
Date Text
2006-07-24 00:00:00 
  
 DERNIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION. DUE TO THE CHANGE OF
 OCCUPANCY AND OWNER IMPACT FEES MAY BE
 REQUIRED
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) GARAGE IS ON LOT #3 AND HAS A
 SEPERATE PCN# PLEASE PROVIDE UNITY OF
 TITLE (SEE ZONING COMMENTS)
  
 4) HISTORIC REVIEW AND STAMP IS REQUIRED
 PRIOR TO BUILDING APPROVAL
  
 5) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 6) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC. LICENCE NUMBER IS
 MISSING FROM ALL BUT STRUCTURAL PAGES
  
 7) PLEASE SEE RED LINED REMARKS TO COVER
 PAGE, NO WHITE OUT, WRONG FLOOD ZONE,
 ETC.
  
 8) PROVIDE THE ROOF SHEATHING SIZE AND
 SPECIAL NAILING ZONES THAT COMPLY WITH
 TABLE 2304.9.1 FBC
  
 9) SHOW COMPLIANCE WITH THE PROVISIONS
 OF 717.2.7 FBC FOR CONCEALED SLEEPER
 SPACES
  
 10) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 ************NOTE*************
 THE FOLLOWING PRODUCT APPROVALS ARE
 REQUIRED FRENCH DOORS W/WO SIDELITES,
 CASEMENT WINDOWS, FIXED TRANSOM WINDOWS,
 AND MULLIONS IF WINDOWS ARE NOT SINGLE
 UNITS.
 ALSO WINDOW WALL PANELS(STOREFRONTS) ARE
 ONLY SMALL IMPACT RATED AND WOULD
 REQUIRE IMPACT PROTECTION (SEE 1609.1.4
 FBC) LOWER 30 FEET SHALL BE LARGE MISSLE
 RATED.
 ROOFING SYSTEM CHOSEN DOES NOT MEET THE
 REQUIRED DESIGN PRESSURES AND ENHANCED
 FASTENING CANNOT BE USED (SEE LIMITATION
 #9
 WHERE POSSIBLE THE CITY OF WEST PALM
 REQUIRES THE STATE OF FLORIDA PRODUCT
 APPROVAL SHEETS
  
 11) THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 12) PROVIDE WINDOW SIZES TO ASCERTAIN
 THAT DESIGN PRESSURES FROM PRODUCT
 APPROVALS ARE MET. ALSO FOR THE GLASS
 BLOCK BE SURE TO KEEP SIZE WITHIN THE
 MAXIMUM WIDTH AND HEIGHT.
  
 13) DRAWING SHOWS FIREPLACE UNDER ROOFED
 PATIO AT GARAGE BUT NO CHIMNEY IS SHOWN
 PLEASE CLARIFY, ALSO SUPPLY
 MANUFACTURERS SPECIFICATIONS
  
 14) COLUMNS C2 ON S/3, IS THIS THE
 TYPICAL MASONARY DETAIL P2 ON DETAIL 10
 S/4 PLEASE CLARIFY
  
 15) PLEASE CLARIFY ELEVATIONS BETWEEN
 ARCHITECTURAL AND STRUCTURAL SEE A/3
 PATIO OPENINGS ARE 11'-4" HIGH AND THE
 ROOF HEIGHT ON SECTION 8 & 9 IS 9'-4" ON
 S/5, ALSO SECTION 7 HAS NO HEIGHT STATED
 BUT THE PARAPET HEIGHT IS THE SAME AS
 THE MAIN GARAGE PARAPET AND DIFFERS FROM
 THE PARAPET HEIGHT ON SECTION 9.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  