| Date |
Text |
| 2007-04-08 10:10:06 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THAT NOT ALL SHEETS ARE SIGNED, |
| | DATED AND SEALED BY THE ENGINEER OF RECORD. |
| | FS 471.025, FAC 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS WERE ISSUED FOR PERMIT |
| | WITH *NOTES REDLINED* AND ATTACHED TO PLANS. PLEASE SEE |
| | TO DATE THAT NO DOCUMENTATION AHS BEEN VERIFIED FOR |
| | COMPLIANCE TO MEET THE EXCEPTIONS OF THE NEC FOR |
| | DISCONNECTING MEANS ETC AS PREVIOUSLY GONE OVER FOR THE |
| | DETACHED BUILDING. |
| | PLEASE SEE 225.31-225.398 |
| | PLEASE SEE THE NOTES BELOW ARE TAKEN FROM THE ISSUED |
| | PLANS AND PERMITS FOR SCOPE OF WORK. |
| | PLEASE PROVIDE COMPLETED DOCUMENTATION FOR EXCEPTION OF |
| | *SAFE PROCEDURES*, *QUALIFIED PERSONNEL* ON-SITE 24/7 |
| | ETC, PAPERWORK AND DOCUMENTATION MUST BE ORIGINAL, |
| | SIGNED, AND NOTARIZED. |
| | IF THIS IS NOT MET THEN PLANS AS ORIGINALLY NOTED WILL |
| | NEED TO BE REVISED TO MEET NEC CODE COMPLIANCE. |
| | |
| | 3) NOTE: PLEASE ALSO SEE THAT AS TO DATE OUR RECORDS DO |
| | NOT INDICATE ANY LOW VOLTAGE PERMIT WHICH HAS BEEN |
| | APPLIED FOR OR ISSUED FOR THIS PROJECT. |
| | PLEASE SEE NOTES REDLINED ON PLANS WHICH MENTION THIS |
| | IS TO BE UNDER A SEPARATE PERMIT. |
| | |
| | |
| | |
| | ************** NOTES REDLINED******* |
| | |
| | *** LOW VOLTAGE WIRING UNDER A SEPARATE PERMIT. |
| | |
| | |
| | **** 1) NOTE: PLEASE KNOW UPON READING RESPONSE FROM |
| | DESIGN TEAM, THIS OFFICE IS WELL AWARE THAT THE |
| | STRUCTURE MAY BE FED WITH OTHER SYSTEMS AS LISTED IN |
| | 225.30.PLEASE SEE PREVIOUS NOTES WHICH WAS WITH |
| | RESPECT TO DISCONNECTING MEANS REQUIRED ETC. PLEASE SEE |
| | THE FOLLOWING EXCEPTION WHICH IS TAKEN DIRECTLY FROM |
| | THE NEC WILL BE REQUIRED TO BE VERIFIED ON SITE.THIS |
| | WAS RED-LINED ON E-5. |
| | "EXCEPTION NO. 1: FOR INSTALLATIONS UNDER SINGLE |
| | MANAGEMENT, WHERE DOCUMENTED SAFE SWITCHING PROCEDURES |
| | ARE ESTABLISHED AND MAINTAINED FOR DISCONNECTION, AND |
| | WHERE THE INSTALLATION IS MONITORED BY "QUALIFIED |
| | INDIVIDUALS", THE DISCONNECTING MEANS SHALL BE |
| | PERMITTED TO BE LOCATED ELSEWHERE ON THE PREMISES " |
| | |
| | ** PLEASE SEE NEC ART: 100 FOR*QUALIFIED PERSON*. ONE |
| | WHO HAS SKILLS AND KNOWLEDGE RELATED TO THE |
| | CONSTRUCTION AND OPERATION OF THE ELECTRICAL EQUIPMENT |
| | AND INSTALLATIONS AND HAS RECEIVED SAFETY TRAINING ON |
| | THE HAZARDS INVOLVED. |
| | EXCERPT FROM HANDBOOK: |
| | "NEW IN THE 2002 EDITION, THE DEFINITION OF THE TERM |
| | QUALIFIED PERSON NOW INCLUDES SAFETY TRAINING. NO |
| | LONGER IS IT ADEQUATE FOR AN ELECTRICAL WORKER TO BE |
| | *FAMILIAR WITH THE HAZARDS INVOLVED*; THE ELECTRICAL |
| | WORKER OF TODAY MUST ALSO HAVE SAFETY TRAINING ON THE |
| | HAZARDS INVOLVED. " |
| | |
| | ** PLEASE KNOW THESE QUALIFIED PERSON(S) SHALL BE |
| | VERIFIED EMPLOYED BY AND ON SITE 24/7, IF THIS CAN NOT |
| | BE VERIFIED, ELECTRICAL INSTALLATION AS SHOWN MAY NEED |
| | TO BE ADJUSTED TO MEET CODE. |
| | THIS PLANS EXAMINER CAN NOT VERIFY AND WILL BE THE |
| | RESPONSIBILITY OF THE ENGINEERING / DESIGN TEAM, |
| | LICENSED ELECTRICAL CONTRACTOR AND ELECTRICAL |
| | INSPECTOR. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |