| 2006-11-03 20:47:30 | ************** NOTES REDLINED******* |
| | |
| | *** LOW VOLTAGE WIRING UNDER A SEPARATE PERMIT. |
| | |
| | |
| | **** 1) NOTE: PLEASE KNOW UPON READING RESPONSE FROM |
| | DESIGN TEAM, THIS OFFICE IS WELL AWARE THAT THE |
| | STRUCTURE MAY BE FED WITHOTHER SYSTEMS AS LISTED IN |
| | 225.30.PLEASE SEE PREVIOUS NOTES WHICH WAS WITH |
| | REPSECT TO DISCONNECTING MEANS REQUIRED ETC. PLEASE SEE |
| | THE FOLLOWING EXCEPTION WHICH IS TAKEN DIRECTLY FROM |
| | THE NEC WILL BE REQUIRED TO BE VERIFIED ON SITE.THIS |
| | WAS RED-LINED ON E-5. |
| | "EXCEPTION NO. 1: FOR INSTALLATIONS UNDER SINGLE |
| | MANAGEMENT, WHERE DOCUMENTED SAFE SWITCHING PROCEDURES |
| | ARE ESTABLISHED AND MAINTAINED FOR DISCONNECTION, AND |
| | WHERE THE INSTALLATION IS MONITORED BY "QUALIFIED |
| | INDIVIDUALS", THE DISCONNECTING MEANS SHALL BE |
| | PERMITTED TO BE LOCATED ELSEWHERE ON THE PREMISES " |
| | |
| | ** PLEASE SEE NECART: 100 FOR "QUALIFIED PERSON". |
| | "QUALIFIED PERSON. ONE WHO HAS SKILLS AND KNOWLEDGE |
| | RELATED TO THE CONSTRUCTION AND OPERATION OF THE |
| | ELECTRICAL EQUIPMENT AND INSTALLATIONS AND HAS RECEIVED |
| | SAFETY TRAINING ON THE HAZARDS INVOLVED. |
| | EXCERPT FROM HANDBOOK: |
| | "NEW IN THE 2002 EDITION, THE DEFINITION OF THE TERM |
| | QUALIFIED PERSON NOW INCLUDES SAFETY TRAINING. NO |
| | LONGER IS IT ADEQUATE FOR AN ELECTRICAL WORKER TO BE |
| | ?FAMILIAR WITH THE HAZARDS INVOLVED?; THE ELECTRICAL |
| | WORKER OF TODAY MUST ALSO HAVE SAFETY TRAINING ON THE |
| | HAZARDS INVOLVED. " |
| | |
| | ** PLEASE KNOW THESE QUALIFIED PERSON(S) SHALL BE |
| | VERIFIED EMPLOYED BY AND ON SITE 24/7, IF THIS CAN NOT |
| | BE VERIFIED , ELECTRICAL INSTALLATION AS SHOWN MAY NEED |
| | TO BE ADJUSTED TO MEET CODE. |
| | THIS PLANS EXAMINER CAN NOT VERIFY AND WILL BE THE |
| | RESPONSIBILTY OF THE ENGINEERING / DESIGN TEAM, |
| | LICENSED ELECTRICAL CONTRACTOR AND ELECTRICAL |
| | INSPECTOR. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL., TO DATE, NO |
| | ONE FROM THE DESIGN TEAM HAS CONTACTED THIS OFFICE FOR |
| | ANY COMMENTS OR QUESTIONS. |
| | |
| | DEWEY PALMER. |
| | ELECTRICAL PLAN REVIEW |
| | [email protected] |
| | 561-805-6717 |