| 2006-09-16 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE SEE SOME NOTES FORM PREVIOUS |
| | REVIEW ARE STILL IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE VALUE FOR SCOPE OF |
| | WORK WAS INCREASED BY THE $120K ON |
| | RESPONSE. THE ADDITIONAL FEE WILL BE |
| | OWED BEFORE PERMIT CAN BE ISSUED. |
| | FEE OWED $1332.00 |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTE WHICH |
| | REQUESTED ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE UPS SYSTEM(S) EQUIPMENT, |
| | ATS EQUIPMENT ETC. |
| | RESPONSE MENTIONS THIS WERE TO BE |
| | SUBMITTED , HOWEVER THESE WERE NOT |
| | SUBMITTED FOR REVIEW. |
| | 110.3,90.7 |
| | |
| | 3) NOTE: PLEASE SEE IT IS STILL UNCLEAR |
| | IF THIS IS CONSIDERED AS "ONE BUILDING" |
| | FROM THE DEFINITIONS AS SETFORTH IN THE |
| | FBC. PLEASESEE DEFINITIONS ,, WALKWAYS, |
| | ENCLOSED, OPEN ETC AND THE EXTEND OF THE |
| | SIZE(S) NEEDED FOR THE CONSIDERATION OF |
| | "ONE BUILDING". PLEASE KNOW, SOME OF |
| | THIS LAYOUT OR INFORMATION MAY BE |
| | SUPPLIED OR SHOWN ON SEPARATE SHEETS |
| | FROM THE ARCHITECT ECT FOR |
| | CLARIFICATION. |
| | 225.31-225.39 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-09-15 00:00:00 | IN ELEC FOR REVIEW. |