| 2006-06-29 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE ADDRESSING SHALL |
| | CORRELATE, AS THE APPLICATION SHOWS 901 |
| | S FLAGLER, THE PCN USED IS FOR 900 S |
| | OLIVE, AND PLANS SHOWS 1101 S OLIVE. |
| | PLEASE KNOW, ALL THESE SHALL CORRELATE |
| | AND ONCE THE "ADDRESS" IS CORRECTED, |
| | PLEASE MAKE SURE ALL TITLE BLOCKS ON ALL |
| | SHEETS ARE CORRECTED. |
| | FAC 61G1-16.004 |
| | |
| | 2) NOTE: PLEASE SEE COVER SHEETS STATES |
| | DESIGN PER 2001 FBC, WHERE WE ARE |
| | CURRENTLY UNDER THE 2004 FBC. |
| | |
| | 3) NOTE: PLEASE SEE PLANS SHALL INCLUDE |
| | ALL THE CURRENT CODES ADOPTED AND IN |
| | AFFECT IN THE STATE OF FLORIDA. |
| | PLEASE SEE THE FOLLOWING CODES SHALL BE |
| | STATED ON PLANS AT A MINIMUM. |
| | NFPA-70 2002, NFPA-101 2003, NFPA-72 |
| | 2002, NFPA-75 2003. |
| | |
| | 4) NOTE: PLEASE SEE VALUE FOR COMPLETE |
| | SCOPE OF WORK SHALL BE ADJUSTED TO |
| | INCLUDE ALL LABOR AND MATERIALS. |
| | PLEASE KNOW, EVEN IF ANY EQUIPMENT IS |
| | SUPPLIED BY THE OWNER. |
| | VALUE AT THIS TIME IS LOW. |
| | FBC ADMIN SECT 108.3 |
| | |
| | 5) NOTE: PLEASE SUBMIT MANUFACTURES |
| | SPECS/CUT SHEETSFOR ALL NEW UPS |
| | EQUIPMENT. |
| | 110.3, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SUBMIT MANUFACTURES |
| | SPECS/CUT SHEETS FOR THE NEW ATS BEING |
| | PROPOSED. |
| | 110.3, FBC106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE RISER MENTIONS TAPS |
| | PER "220.21"? THIS SHOULD BE PER |
| | "240.21" |
| | PLEASE ALSO KNOW, NOTE MENTIONS NOT TO |
| | BE LOCATED MORE THAN 10FT AWAY, HOWEVER |
| | PLEASE KNOW AND NOTE ON PLANS, THAT ITS |
| | THE CONDUCTOR LENGTH NOT THE DISTANCE. |
| | PLEASE ADJUST NOTE. |
| | 240.21, 215.5 |
| | |
| | 8) NOTE: PLEASE CLARIFY PLANS, RISER AS |
| | PLANS SEEM TO BE SHOWING THE FEEDERS |
| | COMING FROM A SEPARATE, DETACHED |
| | BUILDING?? |
| | IF THIS IS THE CASE PLEASE SEE |
| | 225.31-225.39. |
| | PLEASE ADJUST, AND PLEASE VERIFY THE |
| | EXISTING AS THIS DOES NOT SEEM TO MEET |
| | 225.31-225.39 |
| | PLEASE ALSO SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM. |
| | |
| | 9) NOTE: PLEASE PROVIDE VD CALCULATIONS |
| | FOR THE NEW FEEDERS FROM THE EXISTING |
| | MAIN ELECTRICAL RM. |
| | FBC 2004 13-413.1ABC.1 |
| | |
| | 10) NOTE: PLEASE PROVIDE A GROUNDING |
| | RISER FOR ALL EQUIPMENT,UPS AND |
| | ATTACHMENT LOCATION(S). 250.30,250.20, |
| | 645.15 |
| | |
| | ** IMPORTANT** |
| | |
| | PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF THE OLD/VOIDED |
| | SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |