| 2006-06-29 00:00:00 | DENIED |
| | |
| | 1) SPECIFY THE BUILDING HEIGHT AND |
| | NUMBER OF STORIES ON THE PLANS. FBC |
| | 106.1.2 |
| | |
| | 2) SPECIFY THE POSITIVE AND NEGATIVE |
| | WIND PRESSURES FOR THE EXTERIOR OPENINGS |
| | ON THE PLANS. FBC 1603.1.4 |
| | |
| | 3) SHUTTER INSTALLATION ON LARGE OR |
| | MULTISTORY BUILDINGS REQUIRE PRE-STORM |
| | PREPARATION PLANS APPROVED BY THE |
| | CONSTRUCTION SERVICES DEPARTMENT. SEE |
| | #13 OF THE ATTACHED IMPACT PROTECTION |
| | STANDARD. |
| | |
| | 4) THE FASTENER INDICATED (HI-LIGHTED) |
| | ON THE PRODUCT APPROVAL FOR THE STORM |
| | PANELS IS FOR ATTACHMENT TO WOOD. THE |
| | PLANS SPECIFY CONCRETE AND STEEL |
| | CONSTRUCTION. |
| | |
| | 5) PROVIDE A KEY PLAN AND INSTALLATION |
| | SCHEDULE. SPECIFY THE FASTENERS, |
| | FASTENER SPACING, SPANS, VERTICAL OR |
| | HORIZONAL INSTALLATION, ETC. A SAMPLE |
| | INSTALLATION SCHEDULE IS ATTACHED TO THE |
| | IMPACT PROTECTION STANDARD. |
| | |
| | 6) IF THE DOORS ARE REQUIRED FOR EGRESS |
| | EXIT THEY CAN NOT BE SHUTTERED. |
| | |
| | 7) THE FLORIDA COVERSHEET FOR THE ARCH |
| | ALUMNIUM DOORS IS FOR IMPACT RATED DOORS |
| | THE STOREFRONT DOOR NOA IS FOR |
| | NON-IMPACT DOORS. SUBMIT COVERSHEET AND |
| | EVALUATION REPORTS FOR THE SAME PRODUCT. |
| | |
| | 8) THE FLORIDA COVERSHEET FOR THE ARCH |
| | ALUMINUM STOREFRONT PANEL WALLS DOES NOT |
| | MATCH THE NOA THAT WAS SUBMITTED. |
| | COVERSHEET IS FOR IMPACT AND NOA IS FOR |
| | NON-IMPACT. |
| | |
| | 9) PROVIDE BUCK ATTACHMENT DETAILS. |
| | |
| | 10)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |